Section 3 – SR-2 Software Description
Controlling Sensor
Micro Rev
All
HMI Rev
All
Choices
Return, Discharge or Selectable
Factory Set
Return
Exceptions
Description
Modulation provides very smooth
and steady temperature control. Modulation is only
operational in Continuous Mode.
This feature determines the controlling sensor used
during modulation operation, either the Return Air
Temperature Sensor or Discharge Air Temperature
Sensor.
During Return Air Modulation, the discharge air
temperature is limited to the programmed floor limit.
The floor limit is equal to setpoint minus the setting
of the FreshSet Floor Limit feature. This provides
additional protection from freezing for sensitive
loads. If the discharge air temperature reaches the
floor limit, unit control will shift to the discharge air
sensor. Control will automatically revert to the return
air sensor when conditions allow.
During Discharge Air Modulation, the discharge air
temperature is controlled to the setpoint.
Although the Selectable choice appears in the
menu, it is not implemented and should not be used.
FreshSet Modulation Pull Down Option
Micro Rev
All
HMI Rev
All
Choices
Maximum or Floor Limit
Factory Set
Maximum
Exceptions
Only appears if Controlling Sensor =
Return.
Description
This feature determines the
modulation pull down control algorithm used. This
feature is only available with return air temperature
control. The floor limit algorithm is always used with
discharge air control.
If MAX is selected, modulation pull down control is
governed by the 300°F*Minute (160°C*Minute)
algorithm. During MAX pull down, the unit is in full
cool and the discharge air temperature is allowed to
drop below the programmed floor limit for a defined
period of time. This option provides the fastest pull
down while minimizing the potential for product top
freezing.
MAX pull down example: If the discharge air is 15°F
(8°C) below setpoint the unit will operate in full cool
for 20 minutes before entering modulation cool.
(e.g. 15°F x 20 minutes = 300°F*Minutes or 8°C x 20
minutes = 160°C*Minutes)
If FLOOR LIMIT is selected, modulation pull down
control is governed by the Floor Limit pull down
algorithm. During Floor Limit pull down the unit will
operate in high speed but will control the discharge
air temperature to the programmed Floor Limit.
After the pull down conditions are satisfied the unit
will switch to low speed modulation. This option
provides a fast pull down while eliminating the
potential for product top freezing with fragile
commodities.
3-37
31 January 2005
Summary of Contents for SR-2 SmartReefer2
Page 4: ......
Page 7: ...Tab goes here and the next page should be GREEN Section 1 Safety...
Page 8: ......
Page 10: ...Section 1 SR 2 Safety Information 1 2 18 January 2005...
Page 14: ...Section 1 SR 2 Safety Information 1 6 18 January 2005...
Page 15: ...Tab goes here and the next page should be GREEN Section 2 Hardware Description...
Page 16: ......
Page 48: ...Section 2 SR 2 Hardware Description 2 32 31 January 2005...
Page 49: ...Tab goes here and the next 2 pages should be GREEN Section 3 Software Description...
Page 50: ......
Page 96: ...Section 3 SR 2 Software Description 3 46 31 January 2005...
Page 97: ...Tab goes here and the next page should be GREEN Section 4 Operation...
Page 98: ......
Page 181: ...Tab goes here and the next 2 pages should be GREEN Section 5 Diagnostics...
Page 182: ......
Page 266: ...Section 5 SR 2 Diagnostics 5 84 02 February 2005...
Page 267: ...Tab goes here and the next page should be GREEN Section 6 Service Procedures...
Page 268: ......
Page 270: ...Section 6 SR 2 Service Procedure Index Page 2 01 February 2005...
Page 282: ...Section 6 SR 2 Service Procedure A01B Page 6 P41RA01B 31 January 2005...
Page 298: ...Section 6 SR 2 Service Procedure A02A Page 12 P41RA02A 02 February 2005...
Page 318: ...Section 6 SR 2 Service Procedure A03B Page 4 P41RA03B 30 January 2005...
Page 338: ...Section 6 SR 2 Service Procedure A15A Page 4 P41RA15A 30 January 2005...
Page 360: ...Section 6 SR 2 Service Procedure A46B Page 8 P41RA46B 30 January 2005...
Page 366: ...Section 6 SR 2 Service Procedure A48A Page 6 P41RA48A 30 January 2005...
Page 376: ...Section 6 SR 2 Service Procedure A50A Page 6 P41RA50A 31 January 2005...
Page 394: ...Section 6 SR 2 Service Procedure F08A Page 4 P41RF08A 30 January 2005...
Page 398: ...Section 6 SR 2 Service Procedure F09A Page 4 P41RF09A 30 January 2005...
Page 402: ...Section 6 SR 2 Service Procedure G03A Page 4 P41RG03A 31 January 2005...
Page 406: ...Section 6 SR 2 Service Procedure H04A Page 4 P41RH04A 30 January 2005...
Page 407: ...Tab goes here and the next page should be GREEN Section 7 Service Information...
Page 408: ......
Page 410: ...Section 7 SR 2 Information 7 2 02 February 2005...
Page 419: ...Tab goes here and the next page should be GREEN Section 8 Schematics and Wiring Diagrams...
Page 420: ......
Page 422: ...Section 8 SR 2 Drawings 8 2 01 February 2005...
Page 424: ...Section 8 SR 2 Drawings 8 4 01 February 2005...
Page 425: ...8 5...
Page 426: ...8 6...
Page 427: ...8 7...
Page 428: ...8 8...
Page 429: ...8 9...
Page 430: ...8 10...
Page 431: ...8 11...