Section 5 – SR-2 Diagnostics
204 CHECK DISPLAY DISCHARGE AIR SENSOR
Page 1 of 2
Alarm Type
Check Alarm
(Shutdown Alarm during a Pretrip Test).
Associated Alarm
Codes
Alarm Code 04 Check Display Return Air Sensor
Alarm Code 11 Unit Controlling on Alternate Sensor
Alarm Code 13 Sensor Check
Alarm Code 92 Sensor Grades Not Set
Component Description and Location
This sensor is one of two dual discharge air sensors. Both return air sensors must agree within specified limits.
The sensor associated with Alarm Code 204 Check Display Discharge Air Sensor is used for temperature display
by the HMI control panel. The sensor is located next to the control discharge air sensor in the discharge air stream.
It is a graded sensor.
Circuit Description
The discharge air temperature sensor circuit is a two wire circuit. The DTRP-01 (+) wire connects the
microprocessor 35 pin sensor connector J3 pin 22 to the blue sensor wire. The DTRN-01 (-) wire connects the
microprocessor 35 pin sensor connector J3 pin 33 to the brown sensor wire. The sensor wires are routed in the
Sensor Harness. The sensor is hard wired to the sensor harness.
Considerations
1. If the unit is controlling on discharge air temperature, and a problem occurs with either discharge air
sensor, the unit will switch to Return Air Control and Alarm Code 11 Unit Controlling on Alternate Sensor
will be set.
2. Sensor codes must be cleared from the Maintenance Menu before Alarm Code 11 will clear.
3. Sensor grades must be correctly set to the actual grade of the sensor installed. Failure to do so may result
in nuisance alarm codes.
4. Sensors should be positioned to minimize the potential for moisture entry where the wires enter the sensor
shell. Wherever possible, mount sensors with the barrel up and the wires down.
How Alarm is Set
1. The sensor is over or under range for a specified time interval. The sensor reading may return to normal.
Only Alarm Code 204 Check Display Discharge Air Sensor is set.
2. The sensor reading is erratic over time but did not go over or under range. Both Alarm Code 204 Check
Display Discharge Air Sensor and Alarm Code 13 Sensor Check are set. This indicates the sensor was
inaccurate but was not over or under range.
3. The sensor grade is set to 5H. Both Alarm Code 204 Check Display Discharge Air Sensor and Alarm Code
92 Sensor Grades Not Set are set.
4. The temperatures of the control return air sensor and display return air sensor are not within a specified
range. Alarm Code 04 Check (Control) Discharge Air Sensor, 204 Check Display Discharge Air Sensor
and 13 Sensor Check are set if the faulty sensor cannot be determined. If the faulty sensor can be
determined, only the alarm code for that sensor and Alarm Code 13 will be set.
5-82
02 February 2005
Summary of Contents for SR-2 SmartReefer2
Page 4: ......
Page 7: ...Tab goes here and the next page should be GREEN Section 1 Safety...
Page 8: ......
Page 10: ...Section 1 SR 2 Safety Information 1 2 18 January 2005...
Page 14: ...Section 1 SR 2 Safety Information 1 6 18 January 2005...
Page 15: ...Tab goes here and the next page should be GREEN Section 2 Hardware Description...
Page 16: ......
Page 48: ...Section 2 SR 2 Hardware Description 2 32 31 January 2005...
Page 49: ...Tab goes here and the next 2 pages should be GREEN Section 3 Software Description...
Page 50: ......
Page 96: ...Section 3 SR 2 Software Description 3 46 31 January 2005...
Page 97: ...Tab goes here and the next page should be GREEN Section 4 Operation...
Page 98: ......
Page 181: ...Tab goes here and the next 2 pages should be GREEN Section 5 Diagnostics...
Page 182: ......
Page 266: ...Section 5 SR 2 Diagnostics 5 84 02 February 2005...
Page 267: ...Tab goes here and the next page should be GREEN Section 6 Service Procedures...
Page 268: ......
Page 270: ...Section 6 SR 2 Service Procedure Index Page 2 01 February 2005...
Page 282: ...Section 6 SR 2 Service Procedure A01B Page 6 P41RA01B 31 January 2005...
Page 298: ...Section 6 SR 2 Service Procedure A02A Page 12 P41RA02A 02 February 2005...
Page 318: ...Section 6 SR 2 Service Procedure A03B Page 4 P41RA03B 30 January 2005...
Page 338: ...Section 6 SR 2 Service Procedure A15A Page 4 P41RA15A 30 January 2005...
Page 360: ...Section 6 SR 2 Service Procedure A46B Page 8 P41RA46B 30 January 2005...
Page 366: ...Section 6 SR 2 Service Procedure A48A Page 6 P41RA48A 30 January 2005...
Page 376: ...Section 6 SR 2 Service Procedure A50A Page 6 P41RA50A 31 January 2005...
Page 394: ...Section 6 SR 2 Service Procedure F08A Page 4 P41RF08A 30 January 2005...
Page 398: ...Section 6 SR 2 Service Procedure F09A Page 4 P41RF09A 30 January 2005...
Page 402: ...Section 6 SR 2 Service Procedure G03A Page 4 P41RG03A 31 January 2005...
Page 406: ...Section 6 SR 2 Service Procedure H04A Page 4 P41RH04A 30 January 2005...
Page 407: ...Tab goes here and the next page should be GREEN Section 7 Service Information...
Page 408: ......
Page 410: ...Section 7 SR 2 Information 7 2 02 February 2005...
Page 419: ...Tab goes here and the next page should be GREEN Section 8 Schematics and Wiring Diagrams...
Page 420: ......
Page 422: ...Section 8 SR 2 Drawings 8 2 01 February 2005...
Page 424: ...Section 8 SR 2 Drawings 8 4 01 February 2005...
Page 425: ...8 5...
Page 426: ...8 6...
Page 427: ...8 7...
Page 428: ...8 8...
Page 429: ...8 9...
Page 430: ...8 10...
Page 431: ...8 11...