Operating Instructions
64
Diesel Mode operation will briefly be confirmed. If unit
operation is required the diesel engine will start as shown
previously under STARTING THE DIESEL ENGINE.
If the Electric to Diesel Auto-Switch Enabled feature in
Guarded Access is set NO then the unit can also be switched
from Diesel Mode to Electric Mode operation using the Diesel
Selection from the Main Menu as shown later in this section.
Initiating a Manual Defrost Cycle
Defrost cycles are usually initiated automatically based on time
or demand. Manual defrost is also available
Manual defrost is available if the unit is running and the
evaporator coil temperature is less than or equal to 45 F (7 C).
NOTE: If the Rail Alternate feature is set YES defrost is
allowed with an evaporator coil temperature less than or
equal to 55 F (13 C).
Other features such as door switch settings may not allow
manual defrost under some conditions. To initiate a manual
defrost cycle, press the Defrost Key (Figure 63).
Figure 63: Press Defrost Key
The display briefly shows [DEFROST], [PROGRAMMING
DEFROST - PLEASE WAIT] and then [DEFROST
STARTED] (Figure 64).
Figure 64: Defrost Started
ON
OFF
MENU
35
°F
35
SET
SENSORS
GAUGES
POINT
.8
DEFROST STARTED
ON
OFF