TD-1/07-008
34 / 83
o
Assign 1.keypad to A partition, 2.keypad to B partition
31 01: 1, 31 02: 2
o
Close S.P.T and Arm/Disarm from Foreign Keypad feature(if enabled)
10 01 1 , 4 not selected
o
Assign Siren partition to A
11 01 address:1
o
Adjust Siren Cutting time
11 02 =time
o
Select PGM1 type as Siren
13 01 = 6
o
Select PGM1 partitions as B
13 02= 2
o
Enter user phone numbers 06 01-06 address
(When the phone numbers are entered, dialer actives automatically 2
nd
option at address 50 01)
o
Select phone numbers of A Partition 50 17
o
Select phone numbers of B Partition
50 18
7.4. CONNECTING FIRE DETECTOR
Do following steps to connect fire detector to VAP404 Panel ;
o
Connect contact outputs of fire detector to zone and connect power(+) to AUX(+) and power(-) to PGM1
o
It is not recommended to connect more than 2 to the PGM.
o
PGM1 output must be defaulted.
10 02 = 2 is not selected (NO)
o
Select PGM1 type as supply fire detector
13 01 = 5
o
Assign detector reset time in seconds
13 02 = time
o
Select type of zone connected to fire detector contacts
22 03= 6
Note: User can cancel fire alarm by pressing [0 (long)] or by entering user code.
7.5. CONNECTTING FIRE SIREN
Do following steps to connect fire siren to PGM1 output ;
o
Connect siren to PGM1
o
Select PGM1output type (NC/NO)
10 02 =2
o
Select PGM1 as fire siren
13 01 = 4
7.6. AUTOMATIC ARM PARTITIONS on NO ACTIVITY
Do following steps;
o
Select partitions that will be armed
12 07= partitions
o
Set No activity time
12 08= time