TD-1/07-008
43 / 83
To change value
:
LED
10 06 S ........S √
LCD
1-PANEL SETTINGS
→
GENERAL SETTINGS
→
RESET PERMISSION
S S √
S = Multiple choice selection(1,2)
Default value
: All resets are enabled
Example
: To disable code reset do
“ 10 06
1 (OFF)
√ “
o
To assign Partition to ARM Output
6. option in installer address of 10 02 selects type of ARM output(NC/NO).
When selected ARM partitions are armed, ARM output becomes active.
ABCD : 1. option = A partition, 2. option = B partition, 3. option=C partition, 4. option=D partition
S.P.T. : 1.option = Interior 2. option= Window 3. option= Door 4. option= Exterior
It is recommended to select all partitions on S.P.T.(Look at page 34 for detailed description)
Address = 10 07
< IP >
To see value
:
LED
10 07 (wait)
LCD
1-PANEL SETTINGS
→
GENERAL SETTING
→
ARM-OUT SETTING (wait)
PARTITIONS:
To change value
:
LED
10 07 S ........S √
LCD
1-PANEL SETTINGS
→
GENERAL SETTING
→
ARM-OUT SETTING
PARTITIONS: S ........S √
S = Multiple choice selection(1, 2, 3, 4)
Default Value
: 1= A partition, 2=B partition, 3=C partition, 4=D partition
Example
: To activate ARM when first and second partitions are armed do
“ 10 07
1(ON) 2(ON) 3(OFF) 4(OFF)
√ “
o
AC Fail Call Delay
Panel doesn’t dial Central Monitoring Station or User during time entered this address when AC voltage of
panel is off.
Address = 10 08
< IP >
To see value
:
LED
10 08 (wait)
To change value
:
LED
10 08 TT
√
TT
: 2 digit time in minutes( 0~60 minutes)
Default Value : 0 minute
Example
: To set delay time as 30 minutes do
“10 08
30
√ “
o
Cross Zone Timer
Cross zone timer starts when zone trip occurs. First trip on a cross zone will not cause an alarm. If a second
cross zone that is on the same partition (or the same zone if double hit feature is enabled) is violated within
Cross zone timer duration, the panel goes into alarm
and sends both zone alarms and “Intrusion Verifier” code
to Central Monitoring Station(*) “Cross Zone Fault” code is sent to Central Monitoring Station(*) if no any other
violation after first trip on cross zones that are on the same partition occurs within Cross zone timer duration.
Note(*): Don’t forget that codes can be sent to Central Monitoring Station if it is not disabled by installer.
Address = 10 09
< IP >
To see value
:
LED
10 09 (wait)
LCD 1-PANEL SETTINGS
→
GENERAL SETTING
→
CROSS ZONE
TIME: ……..
To change value
:
LED
10 09 Time (enter the time between 0-
255 sec.) √
LCD 1-PANEL SETTINGS
→
GENERAL SETTING
→
CROSS ZONE
TIME: TTT