EVO STAR 60-800
54
Rectifier
Configuration
Tiristor bridge fullcontroll – option 12 or 18 pulse
Nominal voltage
380-400-415Vac, trN +PE
Frequency
50/60 Hz, +/- 10% selectable
Power factor
0.85 inductive @ 100%load @ 400vac
Tolerance on
VDC
+/-1%
Ripple on VDC
<1%
Max charging
batteries current
15 15 15 15 15 15 20 20 20 20 20 20 20
Battery
Rated buffer
charge @ 20°
436V
Voltage
discharge
320VDC (adjustable)
Inverter
Configuration Trifase
bridge IGBT with pwm control
Nominal output
voltage
380-400-415Vac, tN +PE
Transformer Standard
Wave type
Sinusoidal
Output voltage
tolerance
Static stability
+/-1%
Load variation
0%-100%-0%
+/-8%, static stability in 40ms
Load variation
0%-50%-0%
+/-3% static stability in 40ms
100% unbalance
load (IEC62040)
+/-3%
Output voltage
distortion
100% linear load
2% THD max
80% not linear
load (IEC62040)
5% THD max
Crest factor
3:1 load 80%
Voltage
symmetry
100% balanced
load
120+/-1%
100%
unbalanced load
(80%-0-80%)
120 +/-2%
Output
frequency
From internal
quartz
50/60 Hz +/-0.01%
Frequency
windows
+/-5%
Overloading
(on inverter)
125% per 10 minute, 125%-150% per 60 second
Short circuit (on
inverter)
150% of nominal currentel for 60 sec with in limitation system