________________________________________________________________________________
EVO STAR 60-800
26
6 ACTIVATING THE MANUAL BY-PASS
CAUTION! : IF YOU CARRY OUT THIS PROCEDURE INCORRECTLY YOU COULD
DAMAGE THE U.P.S.
THE MANUFACTURER DECLINES ALL RESPONSABILITIES FOR
DAMAGE DUE TO INCORRECT MANOUEVRING.
CAUTION! : DURING THE ENTIRE PERIOD OF FUNCTIONING IN BY-PASS MODE, THE
ELECTRIC EQUIPMENT CONNECTED TO THE OUTPUT OF THE
DEVICE WILL BE SUBJECT TO THE FLUCTUATIONS MAINS
VOLTAGE.
This manual operation transfers the load directly to the mains during maintenance or if the equipment breakdown.
6.1
ACTIVATING THE BY-PASS SHUTTING DOWN THE U.P.S
1.
Verify that led “A” is green .
2.
Press the
button for about 5 seconds; the message “ Turn off U.P.S ” will appear on the display and leds
“C”,”E” and “F” will turn red and the message “UPS stopped” will appear on the display
3.
Turn on the “by-pass switch” breaker and led “D” will be red
4.
Turn off the “Output switch” breaker and led “G” will be red
5.
Turn off the “Reserve switch” breaker
6.
Turn off the “Mains switch” breaker
7.
Turn off the “Battery switch” breaker
RESTORING NORMAL FUNCTIONING FROM THE PREVIOUS CONDITION
:
1.
Turn on the “Reserve switch” breaker, the message “UPS Stopped” will appear on the display, all the synoptic leds
will be red except led “H” remain green; wait till led “A” starts flashing, if this does not happen the supply voltage
is not adequate or the cyclic sense of the phases is incorrect, therefore you must disconnect the equipment, verify
the connections and start this procedure again from the beginning.
2.
Turn on the “Main switch” e “Output switch” breakers, led “B” and led “G” will be green
3.
Turn off the “Manual by-pass” breaker.
4.
Press the
button for about 2 seconds; the message “Switch on procedure started” will appear on the display, if
the procedure has been carried out correctly led “C” and led “E” will be green and the message “UPS in alarm
mode” will appear
5.
Once you have carried out the turning on procedure and that led “C” and “E” are green, it is possible to close the
“Battery switch” breaker and led “D” will be green
6.2 ACTIVATING THE BY-PASS KEEPING THE U.P.S SWITCHED
ON AND BATTERY CHARGING
1.
Verify that led “A” is green
2.
Press keys F6 and F2 at the same time, using the scroll keys select “On reserve” and confirm your choice by
pressing F6; make sure that led “F” become yellow
3.
Turn on the “Manual by-pass” breaker
4.
Turn off the “Output switch” breaker