Falcon Electric, Inc. 

FN2 Series  

Uninterruptible Power Supply 

Installation & User Manual 

 

 

 

 

 

 

 

 

 

© 2020 Falcon® Electric, Inc. All rights reserved. Falcon® and the Falcon Electric logo are registered trademarks of Falcon Electric, Inc. 

All other brand names and trademarks are the property of their respective owners. The information and specifications stated in this document are 

subject to change without notice. 4-2020

 

www.falconups.com

 

Tower Models 

 

  FN2-6K-2TXI 

  FN2-8K-2TXI 

  FN2-10K-2TXI 

Summary of Contents for FN2 Series

Page 1: ...reserved Falcon and the Falcon Electric logo are registered trademarks of Falcon Electric Inc All other brand names and trademarks are the property of their respective owners The information and speci...

Page 2: ......

Page 3: ...Rear Panel 14 Communication Port 15 LCD Display Icons 16 Getting Started 17 Installation 17 UPS Input Terminal Block 18 UPS Output Terminal Block 19 Internal UPS Transformer Schematic 22 Internal UPS...

Page 4: ...tion User Manual Falcon Electric Inc FN2 Series OM480051 Rev C 4 N 1 Parallel Operation 41 Constant Frequency Operation 42 Specifications 43 Electrical 43 Service Warranty 44 Technical Support 44 Warr...

Page 5: ...to unpack install or operate this UPS Warnings When replacing batteries replace with the same number of the following battery NP7 2 12 7Ah or NPW45 12 9Ah CAUTION Risk of Energy Hazard 12V 7 or 12V 9...

Page 6: ...tection for 30 amperes for 6kVA rating or 50 amperes for 8 to 10kVA rating in accordance with the National Electric Code ANSI NFPA 70 CAUTION To reduce the risk of fire connect the UPS only to a circu...

Page 7: ...batteries Please retain the shipping container in the unlikely event the UPS needs to be returned for service The container has been specifically designed to ship the UPS safely Storage If the UPS is...

Page 8: ...minants Avoid direct sunlight Do not install the UPS in a flammable or otherwise hazardous environment Avoid vibration and areas subject to physical impact To prevent overheating keep all ventilation...

Page 9: ...well as detailed operation and configuration of this device UPS Features True on line architecture continuously supplies your critical device with stable regulated transient free pure sine wave AC pow...

Page 10: ...rmal the DC boost will increase the DC voltage to acceptable level for the inverter i Battery Fuse Over current protection for the batteries j Charger Two stage constant current constant voltage charg...

Page 11: ...ediately le a claim for shipping damage with the carrier If you discover damage after acceptance le a claim for concealed damage To le a claim for shipping damage or concealed damage YOU MUST le with...

Page 12: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev C 12 Accessories Kit...

Page 13: ...is within the acceptable window Flashing green LED indicates that the utility input voltage is outside the acceptable window 4 Green LED indicates the bypass input is normal 5 UPS On Alarm Silence but...

Page 14: ...1 Channel A F Cooling Fan G External Battery Connector I Utility Input Breaker CB1 J Bypass Input Breaker CB2 Dual input model only K Maintenance Bypass Switch L Input Output Terminal Block M Mounting...

Page 15: ...tely monitor the power and UPS status The software bundled with the UPS is compatible with many operating systems such as Windows 2000 XP Server 2003 VISTA Server 2008 Windows 7 and Windows 10 For oth...

Page 16: ...o transfer to bypass Bypass abnormal at ECO mode 2 Utility input abnormal 3 Not Used 4 Alarm Silent 5 UPS Output overload 6 Not Used 7 UPS Alarm 8 3 Digit Measurement 8a EPO Emergency Power Off 8b OFF...

Page 17: ...mize battery life a temperature range of 20 C to 25 C 68 F to 77 F is ideal This UPS is designed for use with industrial scienti c or data processing class equipment PCs workstations servers etc The s...

Page 18: ...on Electric Inc FN2 Series OM480051 Rev C 18 UPS Input Terminal Block Input Configuration Table Terminal 1 Terminal 2 Terminal 3 Terminal 4 G1 N1 L12 L11 Utility Ground Utility Neutral L2 Utility Line...

Page 19: ...2 Terminal 3 Terminal 4 Terminal 5 Terminal 6 G2 N22 N11 L22 L11 L12 Ground 0V 120V 0V 120V 88V N L2 Jumper N11 to L22 Not Used L L1 240V Output Output Configuration Table 240V Terminal 1 Terminal 2...

Page 20: ...0V 0V 120V 88V Jumper to N11 L2 Jumper N11 L22 G2 Neutral Not Used L1 The 120Vac output must not be loaded more than 50 of maximum rated UPS output capacity 240V 120V Output Output Configuration Table...

Page 21: ...PS AC source can be supplied to the UPS from the L12 to N1 terminals For 120Vac output only application output terminal N22 must use AWG 8 wire connected to ground Neutral Bonding AC Input Output Curr...

Page 22: ...Internal UPS Transformer Schematic 0V 208V 240V 0V 120V 120V 88V 0V UPS Load Internal UPS Transformer Configurations 0V 208V 240V 0V 120V 120V 88V 0V UPS Load 240V 120V 208V 120V 0V 208V 240V 0V 120V...

Page 23: ...inputs are normal UPSs with parallel function enabled will display figure A1 then figure A2 and then figure B Otherwise the LCD will display figure A1 directly followed by figure B A1 A2 B 3 The UPS i...

Page 24: ...roximately four seconds Then the display will change from figure E1 to figure F if the self test was successful D E1 F 6 If the self test fails the LCD display will change from figure D to figure E2 t...

Page 25: ...displays figure I In case of failure of cold start procedure the UPS will automatically turn off You must then repeat step 1 G H I 2 Check measured values and figures detected by the UPS a If you woul...

Page 26: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev C 26 I1 J K L M N...

Page 27: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev C 27 O O1 P O2...

Page 28: ...1 Q2 2 Press the Next Page button to scroll through the UPS settings The LCD will display in sequence figure Q1 buzzer figure R1 Self test figure S1 Bypass Voltage Windows figure T Output Frequency Sy...

Page 29: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev C 29 S2 T U V1 V2 V3...

Page 30: ...Make sure the UPS is in Bypass Mode Press the on and Next Page buttons simultaneously for approximately three seconds The buzzer will sound twice and the LCD will display figure Q1 indicating that the...

Page 31: ...d ON separately indicate disabled and enabled h Figure Z indicates the last page of settable parameters i After changing settings you must press the Enter button to save all your changes and exit the...

Page 32: ...NCE BYPASS SWITCH FAILURE TO FOLLOW THIS PROCEDURE WILL RESULT IN DAMAGE TO THE UPS OR CONNECTED EQUIPMENT 8 Press the Off button for approximately 5 seconds UPS will emit 2 beeps a UPS is in Bypass M...

Page 33: ...except both Bypass indicators LED and LCD and Utility indicators LED and LCD If the Bypass or Utility is abnormal after the UPS is locked the related LED or will be off and the related LCD symbol or w...

Page 34: ...rcuit Er10 Inverter over current Er11 UPS over temperature Er12 Severe UPS output overload Er14 Fan error Er16 Output parameters set error in parallel system Er17 ID Numbers are in conflict in Paralle...

Page 35: ...ove the short circuit at the EPO terminal then restart UPS Er11 Er33 Remove any objects blocking the ventilation holes Er14 Replace cooling fan Er15 If UPS is in CVCF mode you must restart the UPS Er1...

Page 36: ...e battery life Connect and turn on UPS to a properly rated outlet for at least 12 hours to ensure batteries are in a fully charged state prior to long term storage o Always switch off the UPS when rel...

Page 37: ...ery Service Life Float Trickle Charge The table below provides the typical battery service life during float trickle charge Ambient temperature greatly affects the overall battery life Temperature Per...

Page 38: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev C 38 Battery Replacement REFERENCE SAFETY SECTION OF THIS MANUAL FOR ALL BATTERY SAFETY WARNINGS 6kVA Model 8 to 10kVA Models...

Page 39: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev C 39...

Page 40: ...on Pin 9 Shutdown UPS positive signal Pin 10 Shutdown UPS negative signal Notes The shutdown function will be activated after 6 to 25 VDC is applied between pin 9 and pin 10 for 5 seconds The capacity...

Page 41: ...led by the UPS output load monitoring During normal operation the load is shared equally among the total number of UPSs installed If the total connected load amount is equal to or less than the capaci...

Page 42: ...that require a constant frequency for the applied load The output frequency will not be synched to the input frequency Notes This option requires Bypass Line to be disabled internally Please specify t...

Page 43: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev C 43 Specifications Electrical For latest released version please visit our website at falconups com...

Page 44: ...artment determine service is required you will be given a Return Material Authorization RMA number along with return shipping instructions The RMA number issued must appear on the outside of the shipp...

Page 45: ...r damage caused by i improper installation misuse or neglect ii unauthorized repairs or modifications or use of unauthorized parts iii acts or events outside of Falcon s control such as fire accidents...