Output Configuration Table (120V)
Terminal 1
Terminal 2
Terminal 3
Terminal 4
Terminal 5
Terminal 6
G2
N22
N11
L22
L11
L12
Ground
Jumper to N22
0V
120V
0V
120V
88V
Jumper to L22
N
Jumper to L11
L
Jumper to N22 Jumper to N11
Not
Used
Notes:
•
The maximum current for each terminal is 36 Amps RMS for 6kVA, 65 Amps RMS for 8
to 10kVA.
•
Single Input Configuration UPS, AC source can be supplied to the UPS from the L12 to
N1 terminals.
•
For 120Vac output only application, output terminal N22 must use AWG #8 wire
connected to ground. (Neutral Bonding)
AC Input / Output Current and Wire Recommendation
Model
Maximum
Current
Conductor Selection
6KVA
36 A
Input: Use #8 AWG, 90
°
C copper wire, TRQ: 12 IN LB
Output: Use #8 AWG, 75
°
C copper wire, TRQ: 12 IN LB
8KVA
52A (Input)
40A
(Output)
Input: Use #6 AWG, 90
°
C copper wire, TRQ: 18 IN LB
Output: Use #8 AWG, 90
°
C copper wire, TRQ: 10 IN LB
10KVA
62A (Input)
50A (Output)
Input: Use #4 AWG, 90
°
C copper wire, TRQ: 18 IN LB
Output: Use #6 AWG, 90
°
C copper wire, TRQ: 10 IN LB
120V
Terminal 1
Summary of Contents for FN2 Series
Page 2: ......
Page 12: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev C 12 Accessories Kit...
Page 26: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev C 26 I1 J K L M N...
Page 27: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev C 27 O O1 P O2...
Page 29: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev C 29 S2 T U V1 V2 V3...
Page 39: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev C 39...