TM 514 – COMMON RAIL TEST
Incorrect phase
Sequence
E67
(LED Phase Seq.)
Flashing
When the sequence of
synchronism signals
interruptions does not
follow the RST
sequence.
Network phase
sequence inverted at
the input.
May have been
changed in another
place of the supply
network.
Motor connection is
incorrect.
Power-on.
Reset key.
DIx.
Undervoltage in the
control supply
E70
(LED Fault)
Flashes twice
(LED Ready) Off
Activates when the
control supply voltage
is lower than 93 Vac.
Electronics supply
lower than the
minimum value.
Electronics power
supply with loose
contact.
Electronics power
supply fuse blown.
Power-on.
Reset key.
Auto-reset.
DIx.
Internal By-pass
relay contact Open
E71
(LED Fault)
Flashes 3 times
(LED Ready) Off
When there is a fault
with the internal By-
pass relay contacts at
full voltage.
Loose contact in the
starting cables of the
Internal By-pass
relays.
Defective By-pass
relay contacts due to
an overload.
Incorrect electronic
supply voltage, only
for SSW-07 models
255-412 A.
Power-on.
Reset key.
Auto-reset.
DIx.