Fuel
Dispensers
TATSUNO
EUROPE
‐
Installation
and
User
Manual
,
revision
10,
January
2022
131
5.
OPERATION
5.1.
INSTRUCTIONS
FOR
SAFE
OPERATION
Dispensers
are
complex
devices
that
have
to
secure
a
whole
range
of
difficult
functions.
Therefore,
cleaning
of
the
storage
tanks,
piping
systems
and
inspection
of
the
pumped
medium
cleanliness
must
be
carried
out
before
commissioning.
An
inspection
of
wiring
and
a
check
of
connection
correctness
must
be
performed
before
commissioning
in
order
to
prevent
any
electric
shock
injuries
and
to
ensure
safety
against
explosion.
Smoking
forbidden
Open
flame
use
forbidden
Use
of
mobile
phones
forbidden
NOTICE
‐
>LPG
For
LPG
dispensers/modules,
a
pressure
test
of
the
LPG
dispenser
must
be
performed
with
a
pipeline
system
by
pressure
of
2.5
MPa,
including
a
review,
before
commissioning.
NOTICE
‐
>ADBLUE
AdBlue®
dispensers/modules
must
be
pressurized
at
0.35
MPa
before
commissioning
the
AdBlue®
dispenser
together
with
the
piping
system
in
order
to
perform
a
pressure
test.
WARNING
Dispensers
are
hygienically
harmless
for
the
customer
and
operator.
It
is
advisable
to
protect
your
hands,
for
example,
with
eco
‐
friendly
gloves
during
normal
maintenance
and
during
deliveries.
In
case
of
skin
contact,
wash
the
affected
area
as
soon
as
possible
with
soap
and
water.
In
case
of
eye
contact,
etc.,
seek
medical
attention.
During
deliveries,
avoid
inhalation
of
vapours
of
the
pumped
medium.
CAUTION
It
is
forbidden
to
smoke
and
use
open
fire
in
the
immediate
vicinity
of
the
dispenser.
The
smoking
ban
applies
also
to
passengers
inside
the
vehicle.
It
is
forbidden
to
use
mobile
phones
in
the
immediate
vicinity
of
the
dispenser.
It
is
forbidden
to
pump
into
the
vehicle
tank
while
the
engine
is
running.
CAUTION
‐
>LPG
Technical
and
technological
devices
must
correspond
to
approved
conditions
together
with
regulations
for
safe
operation
and
maintenance
as
well
as
solutions
of
emergencies.
The
device
must
be
fitted
with
carbon
‐
dioxide
extinguishers
according
to
the
fire
‐
safety
solution.
The
LPG
fuel
station
may
only
be
operated
by
demonstrably
trained
persons.
The
“STOP
button”
is
placed
at
the
dispenser
(for
emergency
situations).
The
procedure
in
case
of
fire
or
emergency
is
precisely
defined
in
local
operating
rules
and
regulations
–
the
attendant
must
be
demonstrably
trained
with
regard
to
this.
The
“STOP
line"
must
be
located
at
least
5
meters
from
the
dispenser.
LPG
containers,
piping
and
dispenser
must
be
earthed,
the
grounding
point
for
the
pumping
tank
must
be
established
and
marked.