background image

(© Oct, 2007)

Compact CW Series Installation, Operation & Maintenance Manual

Air Technology Systems, Inc.

4-3

SYMPTOM

PROBABLE CAUSE

RECOMMENDATION

System Short of Capacity

a. Low Chilled Water flow

Check for leaks. Repair and recharge

system.

b. Supply water temperature too high

Check chilled water supply

c. Reduced airflow

Check filters 

d. Dirty Coil

Clear coil fins of debris

Electric Heater

a. Circuit breaker tripped

Check for short circuit, reset circuit

Inoperable

breaker

b. Temperature setpoint too low

Increase temperature setpoint

c. Overheat switch open

Insufficient air flow across heater
elements. Check for dirty filters or
obstructions that may reduce air flow.
Correct or replace as needed.

d. Manual reset overheat safety

Reset manual overheat safety switch

switch tripped

(see item immediately above).

e. Heater element burned out

Check continuity with an ohmmeter
Replace heater element

Hot Water Heater

a. Low hot water flow

Check hot water flow at supply source

Inoperable

Inspect piping for leaks or obstructions

b. Low hot water supply temperature

Check hot water supply

c. Temperature setpoint too low

Increase temperature setpoint

d. Control power interrupted

Check for loose or broken wires

Humidifier Inoperable

a. Water supply has been turned

Connect and/or turn on water supply

Note: 

See Humidifier

off or not connected

Manual for Additional Help

b. Humidifier switch is in “Off” position

Turn switch to “Auto/On” position

c. Electrical connections are loose

Tighten electrical connections

d. Humidifier circuit breaker tripped

Check for over current by the humidifier
electrodes. Drain water from tank and
refill. Reset circuit breaker.

e. Relative humidity is above setpoint.

Adjust humidity setpoint

f. Electrode canister change cylinder

1. Consult humidifier manual

light is on

2. Water conductivity is too low and
water is at the top of the cylinder,
(see next item).

g. Water conductivity is too low

Add a teaspoon of table salt to the water
through the top of the cylinder. Typically
only required on initial start-up.

Summary of Contents for Compact CW Series

Page 1: ...Oct 2007 Compact CW Series Installation Operation Maintenance Manual Air Technology Systems Inc...

Page 2: ...uage for use by anyone other than the owner of the equipment for which this manual is written without the prior written consent of Stulz Air Technology Systems Inc SATS This document contains confiden...

Page 3: ...umidity Sensor 2 5 2 6 6 Remote Water Detector 2 6 2 7 Piping Connections 2 6 2 7 1 Chilled Water Hot Water 2 6 2 7 2 Condensate Drain 2 7 2 7 2 1 Gravity Drain 2 7 TABLE OF CONTENTS 2 7 2 2 Condensat...

Page 4: ...Installation Downflow 2 2 Figure 7 Downflow Configuration TypicalAir Patterns 2 3 Figure 8 Upflow Configuration Typical Air Patterns Top Discharge 2 4 Figure 9 Upflow Configuration TypicalAir Patterns...

Page 5: ...il at a rate that varies proportionally to the amount of cooling required to meet the user selectable tempera ture setpoint Heat from the surrounding air is trans ferred through the finned tubing of t...

Page 6: ...nc s warranty does not cover failures caused by improper installation abuse misuse misapplication improper or lack of maintenance negligence accident normaldeterioration includingwearandtear ortheuseo...

Page 7: ...le of supporting the unit When working on electrical equipment remove all jewelry watches rings etc Always disconnect the main power supply to the equipment at the main power disconnect switch before...

Page 8: ...pply air as required to offset the sensible cooling of the system during the dehumidification cycle and for the automatic heating mode As a standard electric resis tance heating elements are factory i...

Page 9: ...ller when a smoke alarm condition exists 1 6 3 Firestat Optionally mounted in the return air stream a fire detector senses high retun air temperature and signals the controller when a fire alarm condi...

Page 10: ...d inside the air conditioner unless specified otherwise by the customer The filter box or plenum box assem bly if applicable is shipped separately Unpack and store these items in a safe place unless y...

Page 11: ...ocated inside or outside the conditioned space but are designed to supply air to only one room The Compact CW systems are front accessible which allows the units to be placed in a corner or between ca...

Page 12: ...as possible The return inlet is provided with a turned in flange on top of the unit for connection of the ductwork Refer to the installation drawing provided with the unit The connection of ductwork...

Page 13: ...TLET RETURN AIR INLET Figure 8 Upflow Configuration Typical Air Patterns Top Discharge SUPPLY AIR OUTLET RETURN AIR INLET FRONT FREE RETURN REAR DUCTED RETURN Figure 9 Upflow Configuration Typical Air...

Page 14: ...nsate pump may be provided for automatically eliminating condensate and humidifier flush water from the drain pan The conden sate pump is typically installed by the factory inside the A C unit If an o...

Page 15: ...educed by the controller The user may also enter a gradient factor for humidity control Formula Newsetpoint oldsetpoint gradient startvalue actual value Example temperature 70 5 70 0 5 61 60 Example h...

Page 16: ...freezing temperatures The diameter of the drain line should be the full size of the connection NOTE Pour some water into the condensate drain pan s prior to start up This fills the trap and prevents...

Page 17: ...tions are required WARNING Verify power is turned off before making connec tions to the equipment NOTE All wiring must conform to local and national elec trical code requirements Use of copper conduc...

Page 18: ...local and national electrical code requirements 2 7 3 1 Remote Temperature Humidity Sensor The remote temperature humidity sensor requires a three conductor shielded cable with the shield terminated a...

Page 19: ...motor see Figure 14 is supplied with an adjustable sheave pulley to change blower speed and an adjustable base for belt tensioning Use the following procedure to change the blower speed 1 Turn the A...

Page 20: ...cylinder is warm to verify if the humidifier is operational In all cases 1 to 6 hours might be required to see a desired level or rise in humidity in the conditioned space Once room conditions have b...

Page 21: ...ing components as automatic con trols may start them unexpectedly 4 1 1 Compact CW Precision A C Unit 4 1 1 1 Filter The filter is usually the most neglected item in an air conditioning system To main...

Page 22: ...A change cylinder light on the humidifier cabinet will illuminate red when the cylinder requires replacement NOTE The red light may illuminate during initial start up but it doesn t necessarily mean...

Page 23: ...Low hot water flow Check hot water flow at supply source Inoperable Inspect piping for leaks or obstructions b Low hot water supply temperature Check hot water supply c Temperature setpoint too low In...

Page 24: ...ing the Auto On Off Drain switch to the Drain position 4 4 3 When drained push the Auto On Off Drain switch to the Off position 4 Turn off power at the main power disconnect switch 5 The power wires t...

Page 25: ...ges If you do not have established credit with SATS you must provide a freight carrier account number A written or faxed purchase order is required on warranty parts and must be received prior to 12 0...

Page 26: ...Oct 2007 Air Technology Systems Inc Compact CW Series Installation Operation Maintenance Manual NOTES...

Page 27: ...ith water 8 Water supply line connected to humidifier if required 9 Safety pan installed under ceiling mounted equipment if required 10 Filter box installed if required 11 Filter s installed if requir...

Page 28: ...Oct 2007 Air Technology Systems Inc Compact CW Series Installation Operation Maintenance Manual...

Page 29: ..._ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _...

Page 30: ...Oct 2007 Air Technology Systems Inc Compact CW Series Installation Operation Maintenance Manual...

Page 31: ...OB Freight on Board HACR Heating Air Conditioning Refrigeration HP Horse Power Hz Hertz IAQ IndoorAir Quality in w g Inches of Water Gauge KVA Kilo Volt Amps kW Kilowatt MAX CKT BKR Maximum Circuit Br...

Page 32: ...Oct 2007 Air Technology Systems Inc Compact CW Series Installation Operation Maintenance Manual...

Reviews: