background image

(© Oct, 2007)

Air Technology Systems, Inc.

Compact CW Series Installation, Operation & Maintenance Manual

4.3

Field Service

NOTE

Do not attempt to make repairs without the
proper tools.

It may be necessary to perform repairs on the A/C
system. If field repairs are necessary, the following
procedures apply:

1.

All electrical connections should be checked to
ensure they are tight and properly made.

2.

Check all circuit breakers, contacts and wiring.
The contacter should be examined and replaced if
contacts are worn or pitted.

4.3.1

Piping

When replacing components within the cabinet of the
unit, the following consumable materials are recom-
mended: Use Silfos alloy for copper-to-copper (piping
discharge or suction line repairs). Silver solder (Stay-
Silv #45) and flux are to be used on copper-to-brass or
copper-to-steel repairs.

When component replacement is complete, remove all
traces of flux. After any repair, pressure check the
system to check for leaks prior to recharging the
system.

4.3.2

General Common Repairs/
Component Replacement

4.3.2.1 Humidifier Cylinder Replacement

After an extended period of operation a red light will
illuminate on the humidifier cabinet indicating that the
cylinder is completely used and a replacement
cylinder must be installed. The cylinder is disposable
and cylinder life is dependent on water supply condi-
tions and humidifier usage. The following procedures
are to be followed when replacing the cylinder.

CAUTION

 

Failure to replace the cylinder at the end of cyl-
inder life may result in humidifier damage.

NOTE

Decrease the humidity setpoint below ambient
humidity to allow the cylinder to cool down be-
fore removing the cylinder.

1.

Turn off water supply to the humidifier.

2.

Drain the cylinder by pushing the “Auto/On-Off-
Drain” switch to the “Drain” position.

4-4

3.

When drained, push the “Auto On/Off/Drain”
switch to the “Off” position.

4.

Turn off power at the main power disconnect
switch.

5.

The power wires to the cylinder are attached by
cylinder plugs to the electrode pins on top of the
cylinder. Pull these plugs vertically off the pins.

CAUTION

 

The cylinder and steam hose may be hot and
burns may result.

6.

Loosen the steam hose clamp(s) and pull the
steam hose off vertically.

7.

Lift the cylinder straight up to disengage it from
the humidifier.

8.

Place the new cylinder on the side mounting slots
within the unit, ensuring the cylinder mounting
stubs are seated properly.

9.

Replace the cylinder plugs on the pins, ensuring
the white sensor plug goes on the single pin,
which is offset from the others.

10. Ensure the plugs are secured on the pins. If the

plugs are loose, they may be temporarily
squeezed together, however, the plugs must be
replaced since a loose plug could generate
enough heat to melt and destroy the plug.

11. Replace the steam hose and tighten the clamp(s).

12. Turn on main power at the main power disconnect

switch.

13. Push the “Auto On/Off/Drain” switch to the “Auto

On” position.

14. Turn on the water supply to the humidifier.

15. Re-adjust the humidity setpoint.

If the humidifier is to be shut down for an extended
period, always drain the cylinder first. Follow the above
steps (1 through 4) ensuring the “Auto On/Off/Drain”
switch is in the “Off” position. Failure to do this will
drastically shorten the cylinder life.

4.3.2.2 Filter Replacement

The filters are located either internal to the cabinet or
external to the cabinet, depending on the configuration
of the unit. Regardless of location, all filter access
locations, except for the front hinged access door, are
labeled "FILTER ACCESS". Remove the old filter(s).
Insert the new filter(s), ensuring directional airflow
arrows on the filters are correct, then close the access
panel.

Summary of Contents for Compact CW Series

Page 1: ...Oct 2007 Compact CW Series Installation Operation Maintenance Manual Air Technology Systems Inc...

Page 2: ...uage for use by anyone other than the owner of the equipment for which this manual is written without the prior written consent of Stulz Air Technology Systems Inc SATS This document contains confiden...

Page 3: ...umidity Sensor 2 5 2 6 6 Remote Water Detector 2 6 2 7 Piping Connections 2 6 2 7 1 Chilled Water Hot Water 2 6 2 7 2 Condensate Drain 2 7 2 7 2 1 Gravity Drain 2 7 TABLE OF CONTENTS 2 7 2 2 Condensat...

Page 4: ...Installation Downflow 2 2 Figure 7 Downflow Configuration TypicalAir Patterns 2 3 Figure 8 Upflow Configuration Typical Air Patterns Top Discharge 2 4 Figure 9 Upflow Configuration TypicalAir Patterns...

Page 5: ...il at a rate that varies proportionally to the amount of cooling required to meet the user selectable tempera ture setpoint Heat from the surrounding air is trans ferred through the finned tubing of t...

Page 6: ...nc s warranty does not cover failures caused by improper installation abuse misuse misapplication improper or lack of maintenance negligence accident normaldeterioration includingwearandtear ortheuseo...

Page 7: ...le of supporting the unit When working on electrical equipment remove all jewelry watches rings etc Always disconnect the main power supply to the equipment at the main power disconnect switch before...

Page 8: ...pply air as required to offset the sensible cooling of the system during the dehumidification cycle and for the automatic heating mode As a standard electric resis tance heating elements are factory i...

Page 9: ...ller when a smoke alarm condition exists 1 6 3 Firestat Optionally mounted in the return air stream a fire detector senses high retun air temperature and signals the controller when a fire alarm condi...

Page 10: ...d inside the air conditioner unless specified otherwise by the customer The filter box or plenum box assem bly if applicable is shipped separately Unpack and store these items in a safe place unless y...

Page 11: ...ocated inside or outside the conditioned space but are designed to supply air to only one room The Compact CW systems are front accessible which allows the units to be placed in a corner or between ca...

Page 12: ...as possible The return inlet is provided with a turned in flange on top of the unit for connection of the ductwork Refer to the installation drawing provided with the unit The connection of ductwork...

Page 13: ...TLET RETURN AIR INLET Figure 8 Upflow Configuration Typical Air Patterns Top Discharge SUPPLY AIR OUTLET RETURN AIR INLET FRONT FREE RETURN REAR DUCTED RETURN Figure 9 Upflow Configuration Typical Air...

Page 14: ...nsate pump may be provided for automatically eliminating condensate and humidifier flush water from the drain pan The conden sate pump is typically installed by the factory inside the A C unit If an o...

Page 15: ...educed by the controller The user may also enter a gradient factor for humidity control Formula Newsetpoint oldsetpoint gradient startvalue actual value Example temperature 70 5 70 0 5 61 60 Example h...

Page 16: ...freezing temperatures The diameter of the drain line should be the full size of the connection NOTE Pour some water into the condensate drain pan s prior to start up This fills the trap and prevents...

Page 17: ...tions are required WARNING Verify power is turned off before making connec tions to the equipment NOTE All wiring must conform to local and national elec trical code requirements Use of copper conduc...

Page 18: ...local and national electrical code requirements 2 7 3 1 Remote Temperature Humidity Sensor The remote temperature humidity sensor requires a three conductor shielded cable with the shield terminated a...

Page 19: ...motor see Figure 14 is supplied with an adjustable sheave pulley to change blower speed and an adjustable base for belt tensioning Use the following procedure to change the blower speed 1 Turn the A...

Page 20: ...cylinder is warm to verify if the humidifier is operational In all cases 1 to 6 hours might be required to see a desired level or rise in humidity in the conditioned space Once room conditions have b...

Page 21: ...ing components as automatic con trols may start them unexpectedly 4 1 1 Compact CW Precision A C Unit 4 1 1 1 Filter The filter is usually the most neglected item in an air conditioning system To main...

Page 22: ...A change cylinder light on the humidifier cabinet will illuminate red when the cylinder requires replacement NOTE The red light may illuminate during initial start up but it doesn t necessarily mean...

Page 23: ...Low hot water flow Check hot water flow at supply source Inoperable Inspect piping for leaks or obstructions b Low hot water supply temperature Check hot water supply c Temperature setpoint too low In...

Page 24: ...ing the Auto On Off Drain switch to the Drain position 4 4 3 When drained push the Auto On Off Drain switch to the Off position 4 Turn off power at the main power disconnect switch 5 The power wires t...

Page 25: ...ges If you do not have established credit with SATS you must provide a freight carrier account number A written or faxed purchase order is required on warranty parts and must be received prior to 12 0...

Page 26: ...Oct 2007 Air Technology Systems Inc Compact CW Series Installation Operation Maintenance Manual NOTES...

Page 27: ...ith water 8 Water supply line connected to humidifier if required 9 Safety pan installed under ceiling mounted equipment if required 10 Filter box installed if required 11 Filter s installed if requir...

Page 28: ...Oct 2007 Air Technology Systems Inc Compact CW Series Installation Operation Maintenance Manual...

Page 29: ..._ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _...

Page 30: ...Oct 2007 Air Technology Systems Inc Compact CW Series Installation Operation Maintenance Manual...

Page 31: ...OB Freight on Board HACR Heating Air Conditioning Refrigeration HP Horse Power Hz Hertz IAQ IndoorAir Quality in w g Inches of Water Gauge KVA Kilo Volt Amps kW Kilowatt MAX CKT BKR Maximum Circuit Br...

Page 32: ...Oct 2007 Air Technology Systems Inc Compact CW Series Installation Operation Maintenance Manual...

Reviews: