31
ENGLISH
Green Power 2.0
60-80 kVA - Ref.: IOMMASGPXX06-EN 06
ENGLISH
7. CONNECTIVITY AND COMMUNICATION OPTIONS
7.1. MULTILEVEL
COMMUNICATION
Green Power 2.0 is capable of managing different communication channels simultaneously. It is equipped with standard commu-
nication ports and two slots to host additional optional boards.
This gives Green Power 2.0 immediate interfacing and integration flexibility as soon as the unit is installed, with no need for trained
personnel.
The table below lists the possible connections between the UPS and the external devices.
As each channel is independent, simultaneous connections can
be made to satisfy the different levels of signalling and remote
monitoring.
For UPS connected in parallel: all options listed in
this chapter must only be installed on the UPS in
the parallel configured as ICM.
For further information about parallel systems
please refer to the relevant chapter.
3
4
5
2
1
8
9
7
6
7.1-1
RS232/485 pinout
1
Not
connected
2
RX for RS232
3
TX for RS232
4
Data + for RS485
5
GND
6
Data − for RS485
7
Reserved
8
Not
connected
9
+12
V
RS232 for modem pinout
1
Reserved
2
RX for RS232
3
TX for RS232
4
Reserved
5
GND
6
Not
connected
7
RTS
8
CTS
9
+12
V
7-1
L
E
Key
B
Ethernet
port
C
Serial RS232/485 connector
D
Serial RS232 connector for modem
E
Cable trunking for communication cables
F
USB
port
L
Slots for communication cards
L1
Com-slot 1
L2
Com-slot 2
C
D
C
D
L1 L2
B
F