Unit view
11.6. PARALLEL CONFIGURATION SPECIAL FEATURES
11.6.1. Energy saver
Energy Saver
ensures system availability and simultaneously reduces energy consumption. It is available for parallel systems with
more than two units.
Energy Saver
can be activated in:
HMI MAIN MENU > SETTINGS > UPS SETTINGS > PARALLEL SYSTEM > ENERGY
SAVER
. A high speed digital control is used to keep only the units needed to supply the energy to the load in operation. When the
power consumed by the load increases the UPS units needed to supply the increased power requirements switch on immediately.
11.6.2. Intelligent communication module (ICM)
Intelligent Communication Module (ICM) allows the hierarchical supervision both of each unit and the whole system from all displays.
The advantage of using ICM is that the options and the external communication accessories for system monitoring and diagnostics
(i.e. Net Vision, ADC board, etc.) can be installed only on one UPS.
In the UPS parallel configuration, an additional navigation bar is displayed on the mimic panel page, where all connected units appear.
To enter the
MAIN MENU
select the
SYS
icon and press
ENTER
.
To enter the
UNIT MENU
select one of the numbered icons and press
ENTER
.
11. UPS PARALLEL CONFIGURATION
Use the
UP/DOWN
keys to select diff erent unit or system mimic panels
SYSTEM view (
MAIN MENU
)
Selected UNIT number
Units connected in parallel (
UNIT MENU
)
Icon colours:
same as top bar colours (see 5.2-1)
11.6.2- 2
System view
SYSTEM
mimic panel is selected
The SYS icon is selected
The
symbol (number surrounded by four lines) indicates the Unit number of the UPS upon which the display is mounted (the
display is mounted on UPS #1 in this example). The
BATTERY SETTINGS
menu and the
AUTOMATIC STOP PROCEDURE
are
only available on this