41
Green Power 2.0
60-80 kVA - Ref.: IOMMASGPXX06-EN 06
ENGLISH
10. TECHNICAL SPECIFICATION
Models
60
80
Input/Output phases
3/3
3/3
Electrical specification - Input mains
Input mains voltage
Vin
3ph + N 400 -10% +20% (P.F. 1) (up to -40% @ 45% of nominal load)
Input mains frequency
Hz
45-65
Input mains power factor
≥ 0.99
(3)
Total harmonic input current distorsion (THDi)
≤ 3% (@: Pn, Resistive load, Mains THDv = 1%)
Electrical specification - Auxiliary mains
Auxiliary mains voltage
Vin
Nominal output voltage ±15% (±20% if GENSET is used)
Auxiliary mains frequency
Hz
50/60 +/-2% selectable (±8% if GENSET is used)
Electrical specification - External battery
Battery voltage range
V bat
from +/-175
(4)
up to +/-360
(5)
Electrical specification - Output
Output voltage (three phase + neutral)
V
380/400/415
(1)
selectable
Frequency
Hz
50/60 selectable
Nominal apparent power (Sn) (0 °C ÷ 35 °C)
kVA
60
80
Nominal active power (Pn) (0 °C ÷ 35 °C)
kW
60
80
Overload
(@ 25 °C; Vin > 380;
Vbat > 216)
(2)
• 10 minutes
• 5 minutes
• 1 minute
• 30 seconds
kW
67.5
75
81
90
90
100
108
120
Crest factor @ 25 °C
≥ 2.7
Total harmonic output voltage distortion (THDv)
≤ 1% (Ph/Ph); ≤ 2% (Ph/N) (@: Pn, Resistive load)
Environment
Operating temperature
°C
0 to 35 (15 to 25 recommended for longer battery life)
Storage temperature
°C
-5 to +50 °C
Relative humidity
%
95% condensation-free
Altitude (max)
m
1000 without derating (3000 max)
Acoustic noise at 1 m
dBA
< 58 (< 55 rear excepted)
< 59 (< 56 rear excepted)
Required cooling capacity
m
3
/h
510
Dissipated power (max)
W
4240
5382
Dissipated power (max)
BTU/h
14475
18375
Dimensions and Weight - single cabinet
Dimensions (W x D x H)
mm
600 x 800 x 1400
Weight
kg
210
220
Standards
Safety
EN 62040-1/A1, EN 60950-1
Type and performance
EN 62040-3 (VFI-SS-111)
EMC
EN 62040-2 (Category C3)
Product certification
CE - TÜV-SÜD
Protection level
IP20
1. 360 V with Pout = 90% Pn.
2. Initial Condition Pout ≤ 80% Pn
3. Pout ≥ 50% Sn.
4. @ Battery Fully Discharged. Call SOCOMEC support service.
5. @ Battery Fully Charged. Call SOCOMEC support service.