30
Green Power 2.0
60-80 kVA - Ref.: IOMMASGPXX06-EN 06
6.7. EMERGENCY
SHUTDOWN
Should it be necessary to interrupt the continuous power provided by the UPS quickly (emergency shutdown), this can be done by
putting switch
Q3
to position
0
.
The UPS output can only be electrically disconnected by means of Q3.
If the UPS is operating from the maintenance bypass (Q5 in position 1) with the mains present, the emergency
shutdown does not interrupt the power supply to the load. In emergency conditions all power supplies upstream
of the UPS must be disconnected.
6.8. UPS GENERAL POWER OFF
Using a button/switch connected to the ADC (Advanced Dry Contacts) card it is possible to interrupt the continuous power provided
by the UPS (see chapter 7.3).
6. OPERATING PROCEDURES