5. HUMAN MACHINE INTERFACE
5.1. FOREWORD
The HMI (Human Machine Interface) on the UPS door displays information regarding operating status, electrical measurements,
access to control functions and configuration parameters. It includes a colour graphic display and a luminous status bar, and
provides access to:
• mimic panel;
• measurements and alarms;
• changing UPS operating modes and programming battery tests;
• assisted startup and switching on maintenance bypass procedures;
• settings menu;
• list of events and statistics.
5.1-1
Display
ESC button
Exits current page,
aborts operations.
UP button
Scrolls up through the
available menus/values.
UP/DOWN button
Scrolls down through the
available menus/values.
ENTER button
Accesses the currently
displayed menu, accepts/
sends confi gurations and
commands.
Luminous status bar
Changes colour according to UPS status.
-
Flashing red
: imminent UPS shutdown
-
Red
: Load not powered or battery circuit open
-
Flashing yellow
: UPS in standby mode or maintenance alarm is active
-
Yellow
: UPS on battery or the UPS points out a particular working mode
-
Flashing green
: battery test is in progress
-
Green
: the load is supplied
-
Off
: inactive UPS