4. MODES OF OPERATION
4.3. OPERATION IN CONVERTER MODE
In converter mode the UPS can supply a fully stabilised sinusoidal output voltage with a different frequency from the input power
line (50Hz or 60Hz is available as output frequency value).
IMPORTANT!
Only set this mode on UPS units with the auxiliary mains (AUX MAINS) disconnected!
Do not set this mode on UPS units with common mains lines as it could damage the load!
4.4. OPERATION WITH INTERNAL MAINTENANCE BYPASS
If the internal maintenance bypass is activated using the appropriate procedure, the load is powered directly from the maintenance
bypass, while the UPS is separate from the power supply and can be switched off.
This operating mode can be selected for maintenance to be carried out on the system, so that the necessary actions can be
performed by service personnel without having to disconnect the power supply to the load.
4.5. OPERATION WITH MOTOR GENERATOR (GENSET)
Green Power 2.0 can be operated in conjunction with a generator (GENSET) over the ADC interface (see chapter 7.3).
With a generator, the frequency and voltage ranges of the auxiliary mains can be increased to accept the instability of the GE and at
the same time to avoid operation from the battery or risks of out-of-synchronisation switching on to the bypass.