5. HUMAN MACHINE INTERFACE
5.3.6. BATTERY SETTINGS menu
This is the menu for battery configuration. The list can be scrolled down to see the full list of battery settings. If batteries are not
available, only the first element of the list is shown. When one of the battery settings is edited, all settings below in the list have to be
checked and confirmed. The battery settings are saved only when the last battery setting is confirmed.
To change battery configurations enter the menu:
MAIN MENU > SETTINGS > UPS SETTINGS > BATTERIES
.
In the case of UPSs connected in parallel enter the menu:
UNIT MENU > BATTERY SETTINGS
.
These parameters for battery settings are critical: number of cells, capacity, charge current.
Risk of damage to load or batteries.
5.3.7. HISTORY LOG menu
EVENT LIST
menu: it shows the list of UPS alarms and events that have occurred. Last 150 events can be displayed.
Press
UP/DOWN
to scroll the list.
STATISTICS
menu: the system reports some measurements (output load, input apparent power, internal temperature) in graphi-
cal format. These values can be used to analyse the situation over the last 14 days or in shorter periods (last 24 hours, last hour or
last minute). Enter the required menu and press
UP/DOWN
to scroll through different periods. The last page shows the minimum,
maximum and average values of the selected measurement. This information provides an enhanced evaluation of the equipment
operating mode, verify whether certain critical operating situations are repetitive or only random.
COUNTERS
menu
:
provides the number of events (which occurred in the last 14 days) for switches on the battery, overloads and
the number of working hours on genset.
5.3.8. SERVICE
menu
This menu is reserved for support service personnel and holds UPS identification data, utilities for SW upgrades, and utilities for
downloading reports to a USB key.
5.3.9. COMMISSIONING
CODE
To complete equipment activation, a warranty activation code is required. To insert the
Commissioning Code
go to
MAIN MENU > SERVICE > COMMISSIONING CODE
.
If the
Commissioning Code
is not inserted an alert symbol is shown on mimic panel (
).
The
Commissioning Code
is provided directly by the relevant Support Centre upon communication of the serial number. When the
Support Centre is contacted for the
Commissioning Code
, detailed information can be obtained on the UPS functions available
and on scheduled preventive maintenance programmes.