48
Green Power 2.0
60-80 kVA - Ref.: IOMMASGPXX06-EN 06
11. UPS PARALLEL CONFIGURATION
11.6.3.
Sequential start (confi gurable by Socomec service personnel only)
In a parallel configuration a sequential start can be set in all the units. It allows a reduction of the power impact on the mains or GenSet
when the UPS system resumes from battery mode. The delay restart time (from 0 to 65 seconds) can only be set via ASSIST. The
delay restart rectifier (T_delay_start_rect) has to be the same for each module according to the following specification:
T_delay_start_rect = 5000 ms for each module
Sequential start
Module 1
Module 2
Module 3
Module 4
Module 5
Module 6
Delay time
1x 5 s = 5 s
2x 5 s = 10 s
3x 5 s = 15 s
4x 5 s = 20 s
5x 5 s = 25 s
6x 5 s = 30 s