34
Green Power 2.0
60-80 kVA - Ref.: IOMMASGPXX06-EN 06
7. CONNECTIVITY AND COMMUNICATION OPTIONS
7.2.4. E-mail
setting
If the UPS is connected to an ethernet network (through the standard RJ45 10/100 Base-T connector), an e-mail can be automati-
cally sent by the UPS to named recipients, if any events occur.
Possible events are as follows:
1: On Automatic Bypass
2: Rectifier Input Supply Fault
3: UPS Imminent Stop
4: UPS
Overload
5: UPS On Battery
6: Battery
Discharged
7: Temperature
Alarm
8: Customer Input Alarm
9: UPS General Alarm
The end of the event is notified by another e-mail.
The mail notification service can be enabled in the
SETTINGS > MAIL NOTIFICATIONS
web pages:
The e-mail sending policy is defined by the events that have been selected by the user. If a new e-mail occurs, a new email is sent.
All active events are listed in the e-mail body. If the event has been cancelled by the UPS a cancelled event e-mail is also sent.
It is possible to send a test e-mail.
Summary of Contents for Green Power 2.0 60
Page 23: ...23 Green Power 2 0 60 80 kVA Ref IOMMASGPXX06 EN 06 ENGLISH 5 HUMAN MACHINE INTERFACE 3...
Page 42: ......
Page 43: ...Green Power 2 0 P a r a l l e l C o n f i g u r a t i o n...
Page 49: ......
Page 50: ......
Page 51: ......