39
ENGLISH
Green Power 2.0
60-80 kVA - Ref.: IOMMASGPXX06-EN 06
ENGLISH
9.2. UPS
ALARMS
• A01: BATTERY ALARM
Failure or problem on the battery circuit. Check the battery switch is closed.
• A18: OVERLOAD BLOCKING INVERTER
Reduce the load rate applied to the UPS and reset the alarms.
• A20: WRONG CONFIGURATION
Error in the configuration parameters. Please contact the support service.
• A30: UPS STOPPED FOR OVERLOAD
Reduce the load rate applied to the UPS and reset the alarms.
• A42: REMOTE SERVICE ALARM
This alarm indicates that a critical anomaly has occurred on the UPS. Where a maintenance contract with the Remote Monitoring
option is in place, the procedure for analysing the UPS via remote connection will be automatically activated by your service centre
provider.
• A44: PERIODIC SERVICE CHECK UP
The equipment must undergo regular inspections by the support service in order to ensure optimum performance and efficiency. If the
Scheduled Inspection
signal appears (
) on the mimic panel, the equipment should be inspected by a suitably trained technician.
• A51: OPTION BOARD GENERAL ALARM
Check if the optional cards are correctly inserted in the slots.
• A59: BATTERY CIRCUIT OPEN
Battery switch open.
• A60: FAN FAILURE
Fault in the ventilation system. Check that the air inlet at the front and the air outlet at the back of the UPS are not obstructed.
9. TROUBLESHOOTING