Open Gen Output
Control generator to off load.
31
1#Acc Load Close
Two Accs
:
Control 1# accumulator to take load.
32
1#Acc Load Open
Two Accs
:
Control 1# accumulator to off load.
33
Start Relay
34
Fuel Relay
Action when genset start and disconnect when
genset stop completely.
35
Reserved
36
37
38
39
40
ECU Stop
Used for ECU engine and control its stop.
41
ECU Power
Used for ECU engine and control its power.
42
Reserved
43
Crank Success
Close when detects a successful start signal.
44
Reserved
45
Reserved
46
47
48
Common Alarm
Action when genset common warning, common
shutdown, common trips alarm.
49
Common Trip and Stop
Action when common trip and stop alarm.
50
Common Shutdown
Action when common shutdown alarm.
51
Common Trip Alarm
Action when common trips alarm.
52
Common Warn Alarm
Action in common warning alarm.
53
Reserved
54
Battery High Volts
Action when battery’s over voltage warning alarm.
55
Battery Low Volts
Action when battery’s low voltage warning alarm.
56
Charge Alt Fail
Action when charge failure warning alarms.
57
1#Acc Charge Close
Control 1# accumulator charge switch to close.
58
1#Acc Charge Open
Control 1# accumulator charge switch to open.
59
Measuring Gen Volts
Two accumulator system detect the Gen voltage or
2# Accumulator Voltage effectively.
60
ECU Warn
Indicate ECU sends a warning signal.
61
ECU Shutdown
Indicate ECU sends a shutdown signal.
62
ECU Com Fail
Indicate controller not communicates with ECU.
63
2#Acc Charge Close
Control 2# accumulator charge switch to close.
64
2#Acc Charge Open
Control 2# accumulator charge switch to open.
65
1# Acc. Over Voltage
Warn
66
1# Acc. Under Voltage