HGM7110DC Genset Controller
HGM7110DC Genset Controller Version: 1.0 2014-09-27 Page
25
of
68
No.
Type
Description
16
Level Sensor Open
Circuit
When the controller detects that the level sensor is open
circuit and the acti
on select “Shutdown”, it will initiate a
shutdown alarm.
17
Flexible Sensor 1
Open Circuit
When the controller detects that the flexible sensor 1 is open
circuit and the action select “Shutdown”, it will initiate a
shutdown alarm.
18
Flexible Sensor 1
High
When the controller detects that the sensor 1 value has
exceeded the pre-set value, it will initiate a shutdown alarm.
19
Flexible Sensor 1
Low
When the controller detects that the sensor 1 value has fallen
below the pre-set value, it will initiate a shutdown alarm.
20
Flexible Sensor 2
Open Circuit
When the controller detects that the flexible sensor 2 is open
circuit and the action select “Shutdown”, it will initiate a
shutdown alarm.
21
Flexible Sensor 2
High
When the controller detects that the sensor 2 value has
exceeded the pre-set value, it will initiate a shutdown alarm.
22
Flexible Sensor 2
Low
When the controller detects that the sensor 2 value has fallen
below the pre-set value, it will initiate a shutdown alarm.
23
Digital Input
When digit input port is set as shutdown and the alarm is
active, it will initiate a shutdown alarm.
24
1#Acc. Over Voltage
When the controller detects that the 1# accumulator battery
voltage has exceeded the pre-set value, it will initiate a
shutdown alarm.
25
1#Acc.
Under
Voltage
When the controller detects that 1# accumulator voltage has
fallen below the pre-set value, it will initiate a shutdown alarm.
26
Charge Over Current
When the controller detects that the accumulator current has
exceeded the pre-set v
alue and the action select “Shutdown”,
it will initiate a shutdown alarm.
27
Charge Over Time
If the charging is not finished within the preset time, and the
action select “Shutdown”, it will initiate a shutdown alarm.
28
Charge Fault
If GOV output is 100%, and the charge current has fallen
below the rated charge current, it will initiate a shutdown
alarm.
29
Two Acc. Fault
In Two Accumulator mode, if both accumulator are satisfy the
start requirement, it will initiate a shutdown alarm.
30
2#Acc. Over Voltage
When the controller detects that the 2# accumulator battery
voltage has exceeded the pre-set value, it will initiate a
shutdown alarm.
31
2#Acc.
Under
Voltage
When the controller detects that 2# accumulator voltage has
fallen below the pre-set value, it will initiate a shutdown alarm.