HGM7110DC Genset Controller
HGM7110DC Genset Controller Version: 1.0 2014-09-27 Page
32
of
68
No.
Items
Parameters
Defaults
Description
(0-3600) s
5
Delay
11
2#
Under
Voltage Stop
(0-1)
0
0: Disable; 1: Enable
(0-1000) %
92
Set Value
(0-3600) s
5
Delay
12
2#
Over
Voltage Stop
(0-1)
0
0: Disable; 1: Enable
(0-1000) %
118
Set Value
(0-3600) s
5
Delay
13
Temperature
Coefficient
(2-5)mV/
℃
4
Used for calculating the accumulator
voltage after the compensation: Vtc =
Vn
– Tc*N(T-20).
Vtc: Accumulator voltage after the
compensation;
Vn: Accumulator voltage before the
compensation;
Tc: Compensation Coefficient;
N: Cell Count
;
T: Temperature Value
;
14
Charge
Start
Volt
(0-1000) %
97
Set Value
(0-3600) s
5
Delay
15
Charge
Stop
Volt
(0-1000) %
112
Set Value
(0-3600) s
5
Delay
16
Charge
Stop
Mode
(0-2)
0
0:Charge Current + Volt
;
1: Charge
Delay
17
Constant
Charge Volt
(0-1000) %
110
The accumulator charging mode is
“Constant Voltage” if the charging
voltage after the compensation has
reached the set value.
18
Con-Curr.
Charge
Current
(0-200)A
50
The charging current during “Constant
Current Mo
de”.
19
Constant
Charge Time
(0-300)h
8
In Auto mode, choose “Charge Delay”
as its “Charge Stop Mode”. If the
genset enters into the “Constant
Voltage mode”, it will stop after the
charge delay has expired.
20
Charge
Stop
Current
(0-1000) %
40
In Auto mode,
choose “Charge
CVoltage” as its “Charge Stop