HGM7110DC Genset Controller
HGM7110DC Genset Controller Version: 1.0 2014-09-27 Page
27
of
68
6.4 TRIP ALARM
On initiation of the trip condition the controller will de-energize the
‘
Close Generator
’
Output
without stop the generator.
Trip alarm as following,
No.
Type
Description
1
Gen Over Current
When the controller detects that the genset current has
exceeded the pre-
set value and the action select “Trip”, it will
initiate a trip alarm.
2
Digital Input
When digit input port is set as
“Trip” and the alarm is active, it
will initiate a trip alarm.
3
Charge Over Current
When the controller detects that the accumulator current has
exceeded the pre-
set value and the action select “Trip”, it will
initiate a trip alarm.
4
Charge Over Time
If the charging is not finished within the preset time, and the
action select “Trip”, it will initiate a trip alarm.