HGM7110DC Genset Controller
HGM7110DC Genset Controller Version: 1.0 2014-09-27 Page
16
of
68
exceeded the “constant voltage value”, enter into the “Constant Voltage Charge” status
and this status will last for preset time.
Automatic Stop Sequence,
1) When the genset is charged or w
hen the “Remote Start” signal is removed, the Stop
Delay is initiated.
Once this “stop delay” has expired, the Generator Breaker will open and
the “Cooling Delay” is then initiated.
2)
After the “Cooling Delay”, "Fail to Stop Delay" begins, fuel relay is de-energized, complete
stop is detected automatically.
3)
When generator is stop completely, “After stop” delay will be initiated. Otherwise, fail to
stop alarm is initiated and the corresponding alarm information is displayed on LCD
display. (If generator is stop successfully after “fail to stop” alarm has initiated, “After stop”
delay will be initiated and the alarm will be removed).
4) Generator is placed into its standby mode aft
er its “After stop” delay.