HGM7110DC Genset Controller
HGM7110DC Genset Controller Version: 1.0 2014-09-27 Page
35
of
68
No.
Items
Parameters
Defaults
Description
12
Fail to Stop
Delay
(0-3600)s
20
Time between ending of cooling delay
and stopped.
13
After
Stop
Time
(0-3600)s
0
Time between genset stopped and
standby.
Engine Setting
1
Engine Type
(0-39)
0
Default:
Conventional
Engine(not
J1939)
When connected to J1939 engine,
choose the corresponding type.
2
Flywheel
Teeth
(10-300)
118
Tooth number of the engine, for
judging
of
starter
separation
conditions and inspecting of engine
speed.
See
the
installation
instructions.
3
Rated Speed
(0-6000)RPM
1500
Offer
standard
to
judge
over/under/loading speed.
4
Loading
Speed
(0-100)%
90
Setting value is percentage of rated
speed. Controller detects when it is
ready to load. It won’t enter into
“Constant Charging Mode” when
speed is under loading speed.
5
Loss of Speed
Signal
(0-3600)s
5
Time from detecting speed is 0 to
confirm the action.
6
Loss of Speed
Signal Action
(0-1)
0
0:Warn; 1:Shutdown
7
Over
Speed
Shutdown
(0-200)%
114
Setting value is percentage of rated
speed and delay value can be set.
8
Under Speed
Shutdown
(0-200)%
80
9
Over
Speed
Warn
(0-200)%
110
Setting value is percentage of rated
speed, delay value and return value
can be set.
10
Under Speed
Warn
(0-200)%
86
11
Battery Rated
Voltage
(0-60.0)V
24.0
Standard for detecting of over/under
voltage of battery.
12
Battery
Over
Volts
(0-200)%
120
Setting value is percentage of rated
voltage of battery; delay value and
return value can be set.
13
Battery Under
Volts
(0-200)%
85
14
Charge Alt Fail (0-60.0)V
8.0
In normal running, when charger