HGM7110DC Genset Controller
HGM7110DC Genset Controller Version: 1.0 2014-09-27 Page
36
of
68
No.
Items
Parameters
Defaults
Description
D+(WL) voltage under this value,
charge failure alarm will be initiated.
15
Start Attempts
(1-10) Times
3
Max. Crank times of crank attempts.
When reach this number, failure alarm
will be initiated.
16
Crank
Disconnect
(0-2)
0
See form 5
There
are
2
conditions
of
disconnecting starter with engine.
Each condition can be used alone and
simultaneously to separating the start
motor and genset as soon as possible.
18
Disconnect
Engine Speed
(0-200)%
24
Setting value is percentage of rated
speed. When generator speed higher
than the set value, starter will be
disconnected. See the installation
instruction.
19
Disconnect Oil
Pressure
(0-1000)kPa
200
When generator oil pressure higher
than the set value, starter will be
disconnected. See the installation
instruction.
Load Setting
1
Rated Current
(5-6000) A
500
Rated load current
2
Over Current
Enable
(0-1)
1
0: Disable
1: Enable
3
Over Current
(0-200) %
120
4
Over Current
Action
(0-3)
0
0: Warn; 1: Shutdown;
2: Trip and Stop; 3: Trip
5
Over Current
Type
(0-1)
0
6
Type 1 (Delay) (0-3600) s
10
7
Type
2
(Multiply)
(1-36)
36
8
Current Input
Mode
(0-2)
0
0: 1-Iacc 2-Iload
;
1: 1-Igen 2-Iload
;
2: 1-Igen 2-Iacc.
9
Current
1
Curve Type
(0-1)
0
0: 4-20mA
1: 0-5V
10~
25
Current
1
Curve
Contents
X(0-32762)m/V
0
Custom (x0,y0),(x1,y1),
Y(0-32767)A
0