HGM7110DC Genset Controller
HGM7110DC Genset Controller Version: 1.0 2014-09-27 Page
48
of
68
Accumulator.
17
Auto Mode Lock
When input is active, controller enters into Auto Mode;
all the keys except
are inactive and there is
in the right of first row in LCD.
18
Auto Mode Invalid
When input is active, controller won’t work under Auto
Mode.
key and simulate auto key input does not
work.
19
Reserved
20
Reserved
21
Inhibit Alarm Stop
All shutdown alarms are prohibited except emergence
stop.(i.e. battle mode or override mode)
22
Aux Instrument Mode
All outputs are prohibited in this mode.
23
Reserved
24
Reset Maintenance
Controller will set maintenance time and date as default
when input is active.
25
Reserved
26
Aux. High Temp
Connect to sensor digital input.
27
Aux. Low OP
Connect to sensor digital input.
28
Remote Start
(On Load)
In Auto mode, when input is active, can start genset
automatically and with load when genset is normal
running; when input is inactive, can stop genset
automatically.
29
Reserved
30
Aux. Manual Start
In Manual mode, when input is active, can start genset
automatically; when input is inactive, can stop genset
automatically.
31
1#Acc.Charge Closed
Connect to the auxiliary point of 1# accumulator.
32
2#Acc.Charge Closed
Connect to the auxiliary point of 2# accumulator.
33
Simulate Stop key
An external button; can be connected to simulate panel
button.
34
Simulate Manual key
35
Reserved
36
Simulate Auto key
37
Simulate Start key
38
Simulate Gen Load key
39
Reserved
40
Reserved
41
Reserved
42
Reserved
43
Simulate Raise Key
An external button; can be connected to simulate panel