HGM7110DC Genset Controller
HGM7110DC Genset Controller Version: 1.0 2014-09-27 Page
23
of
68
No.
Type
Description
16
Low Oil Pressure
When the controller detects that the oil pressure has fallen
below the pre-set value, it will initiate a warning alarm.
17
Level Sensor Open
Circuit
When the controller detects that the level sensor is open
circuit and the action select “Warn”, it will initiate a warning
alarm.
18
Low Fuel Level
When the controller detects that the fuel level has fallen below
the pre-set value, it will initiate a warning alarm.
19
Flexible Sensor 1
Open Circuit
When the controller detects that the flexible sensor 1 is open
circuit and the action select “Warn”, it will initiate a warning
alarm.
20
Flexible Sensor 1
High
When the controller detects that the sensor 1 value has
exceeded the pre-set value, it will initiate a warning alarm.
21
Flexible Sensor 1
Low
When the controller detects that the sensor 1 value has fallen
below the pre-set value, it will initiate a warning alarm.
22
Flexible Sensor 2
Open Circuit
When the controller detects that the flexible sensor 2 is open
circuit and the action select “Warn”, it will initiate a warning
alarm.
23
Flexible Sensor 2
High
When the controller detects that the sensor 2 value has
exceeded the pre-set value, it will initiate a warning alarm.
24
Flexible Sensor 2
Low
When the controller detects that the sensor 2 value has fallen
below the pre-set value, it will initiate a warning alarm.
25
Digital Input
When digit input port is set as warning and the alarm is active,
it will initiate a warning alarm.
26
GSM COM Failure
When GSM is enable but the controller couldn’t detect GSM
module, it will initiate a warning alarm.
27
1#Acc. Over Voltage
Warn
When the controller detects that the 1# accumulator battery
voltage has exceeded the pre-set value, it will initiate a
warning alarm.
28
1#Acc.
Under
Voltage Warn
When the controller detects that 1# accumulator voltage has
fallen below the pre-set value, it will initiate a warning alarm.
29
2#Acc. Over Voltage
Warn
When the controller detects that the 2# accumulator battery
voltage has exceeded the pre-set value, it will initiate a
warning alarm.
30
2#Acc.
Under
Voltage Warn
When the controller detects that 2# accumulator voltage has
fallen below the pre-set value, it will initiate a warning alarm.
31
Charge Over Current
When the controller detects that the accumulator current has
exceeded the pre-
set value and the action select “Warn”, it will
initiate a warning alarm.
32
Charge Over Time
If the charging is not finished within the preset time, and the
action select “Warn”, it will initiate a warning alarm.