HGM7110DC Genset Controller
HGM7110DC Genset Controller Version: 1.0 2014-09-27 Page
39
of
68
No.
Items
Parameters
Defaults
Description
Configure Input Ports
Configure Input
1
1
Contents
Setting
(0-50)
28
Remote start (on load). See form 3
2
Active Type
(0-1)
0
0: Closed to active
1: Open to active
Configure Input
2
1
Contents
Setting
(0-50)
26
High temperature shutdown
See form 3
2
Active Type
(0-1)
0
0: Closed to active
1: Open to active
Configure Input
3
1
Contents
Setting
(0-50)
27
Low oil pressure shutdown
See form 3
2
Active Type
(0-1)
0
0: Closed to active
1: Open to active
Configure Input
4
1
Contents
Setting
(0-50)
0
User defined. See form 3
2
Active Type
(0-1)
0
0: Closed to active
1: Open to active
3
Arming
(0-3)
2
0: From safety on 1: From starting
2: Always 3:Never
4
Active Actions
(0-4)
0
0: Warn; 1: Shutdown; 2:Trip and stop
3:Trip 4: Indication
5
Active Delay
(0-20.0)s
2.0
Time from detecting active to confirm
6
Description
LCD display detailed contents when
the input is active.
Configure Input
5
1
Contents
Setting
(0-50)
0
User defined .See form 3
2
Active Type
(0-1)
0
0: Closed to active
1: Open to active
3
Arming
(0-3)
2
0: From safety on 1: From starting
2: Always 3:Never
4
Active Actions
(0-4)
1
0: Warn; 1: Shutdown; 2:Trip and stop
3:Trip 4: Indication
5
Active Delay
(0-20.0)s
2.0
Time from detecting active to confirm