HGM7110DC Genset Controller
HGM7110DC Genset Controller Version: 1.0 2014-09-27 Page
26
of
68
6.3 TRIP AND STOP ALARM
On initiation of the trip and stop condition the controller will de-energize the
‘
Close Generator
’
Output to remove the load from the generator. Once this has occurred the controller will start
the Cooling delay and allow the engine to cool before shutting down the engine.
No.
Type
Description
1
Gen Over Current
When the controller detects that the genset current has
exceeded the pre-
set value and the action select “Trip and
Stop”, it will initiate a trip and stop alarm.
2
Maintenance Due
When count down time is 0 and the action select
“Trip and
Stop”, it will initiate a trip and stop alarm.
3
Digital Input
When digit input port is set as
“Trip and Stop” and the alarm is
active, it will initiate a trip and stop alarm.
4
Charge Over Current
When the controller detects that the accumulator current has
exceeded the pre-
set value and the action select “Trip and
Stop”, it will initiate a trip and stop alarm.
5
Charge Over Time
If the charging is not finished within the preset time, and the
action select “Trip and Stop”, it will initiate a trip and stop
alarm.