8. Communication with machine control unit
- 104 -
951-170-218-EN
Version 06
8.2.3.4 Switching an external additional
valve (output byte 0, bit 6)
An additional valve can be controlled via
output 6 on the MQL control unit.
The additional valve is controlled via output
byte 0, bit 6 (see Chapter 8.2.3).
Automatic control of the additional valve can
also be selected using DIP switch 1,
in which case the additional valve is switched
based on the ball valve (Chapter 8.2.3) with
the inverse signal from the ball valve.
8.2.3.5 Switching an external ball valve
(output byte 0, bit 7)
A ball valve can be controlled via output 7 on
the MQL control unit.
The ball valve is controlled via output byte 0,
bit 7 (see Chapter 8.2.3).
8.2.3.6 Calling the lubrication programs
(output byte 1, bits 0-5)
Lubrication programs are called using bits 0
to 5 in output byte 1.