Adding a New Sensor into Service
80
SKF Wireless Machine Condition Sensor
Service Manual
Turn on the new sensor within the
range of the commissioning network.
Open the
Operating Modes
web page.
A yellow icon with a small wrench will
display while the new sensor is joining
the network.
Wait until the sensor joins the
network. The sensor’s yellow icon in
the
Com. Status
column will turn
green
when it joins
.
The sensor will appear in the Device
Manager hierarchy as the batch
service runs.
OR
Right-click the gateway in the Device
Manager hierarchy and execute a
Find
sensors
command.
In the Device Manager
Gateway
>
Admin
tab, enter the production
Network ID in the
Network Id
field.
Click
Exchange Network Id
to send
the production Network ID to the
gateway network manager and its
connected sensors.
Next, enter the production network
Join Key in the
Join Key
field.
Click
Exchange Join Key
to send the
production Join Key to the gateway
network manager and its connected
sensors.