The P+F Gateway’s Web Page
P+F Gateway’s Installation Torque
22
SKF Wireless Machine Condition Sensor
Service Manual
The Production Network Settings
You can follow the same steps shown above in the section, “Steps to configure a
commissioning gateway,” to modify the gateway’s
network join settings from the
factory
defaults to the final customized settings. However, the network settings modified in this
way are applied
only
to the gateway.
The gateway will
not
propagate
modified network join
settings to the sensors.
Only
the
Device Manager software enables you to change the gateway settings and also
propagates the new settings to all sensors in the network. This procedure is presented
in
Chapter 5, Changing the Network ID and Join Key
.
P+F Gateway’s Installation Torque
The table below provides a guide to tightening the cable glands and cover in order to
maintain the gateway’s IP rating.
Installation Torque for Cable Glands
Type of Cable Glands
2.5 Nm (22 lb-in.)
Plastic
4.11 Nm (36 lb-in.)
Nickel plated brass
4.11 Nm (36 lb-in.)
Stainless steel
Installation Torque for Housing Cover
2.5 Nm (22 lb-in.)