SKF Wireless Machine Condition Sensor
57
Service Manual
6
Troubleshooting XML Import to Analyst
WARNING!
You must use SKF @ptitude Analyst 2012 (7400) MR2 with an XML
Import fix or later version. This version fixed an issue concerning Analyst rejecting
Command 93 overall or waveform measurements due to conflicting DTS.
Refer to the
Wireless Sensor Device Manager 8800 User Manual
for full instructions
on how to set up and enable data export from Device Manager to Analyst. This Service
Manual offers troubleshooting tips for pursuing XML import problems in Analyst.
If
Analyst is not showing data for the POINTs of a sensor,
follow the steps below.
Start by checking the XML import
setup. In Analyst, go to
Customize
>
Configure XML Import
.
The XML Import Configuration dialog
opens.
Is the
Enable processing
check box
selected?
Yes
– Proceed to the next step.
No
– Enable processing.
Verify the Analyst
Input directory
path
matches the WSDM SKFExportFolder
key value in the
Settings.config
file.
Yes
– Proceed to the next step.
No
– Correct the input directory path
so they match. If the
Settings.config
file is changed, restart Device
Manager.
Then, click
Export node information
to re-export the node data to the
correct folder. (
Plant > Export
tab,
Export node information
button.)
Settings.config
file :
<add key="SKFExportFolder" value="C:
\WSDM_Export\
"/>