The P+F Gateway’s Web Page
Comparing P+F with Emerson Gateways
SKF Wireless Machine Condition Sensor
23
Service Manual
Comparing P+F with Emerson Gateways
The table below presents a couple of known differences between the P+F gateway
versus an Emerson gateway. The compatibility of Device Manager and the Emerson
gateway is still under investigation.
P+F Gateway
Emerson Gateway
All gateway functions described
for CMWA 8800 in the
Wireless
Machine Condition Sensor
Setup Guide
and the
Wireless
Sensor Device Manager User
Manual
should work.
The functions in the Device Manager
Gateway
/
Admin
tab do not work.
Supports Command 93 for
caching measured values in
gateway memory. Publishes the
last 12 PV (Velocity RMS), SV
(Env.Acc.Pk-Pk), TV
(Temperature) values at 20 min
intervals in a 60 min cycle for
trending. Measurements have
the accurate date/time stamp
of
when they were sampled.
Does not cache Command 93 data. Command 9
must be used to publish trend values. The gateway
date/time stamps the measur
ements when the
values are received. The stamps may be off by as
much as one cyclic update interval.