The P+F Gateway’s Web Page
Preparing a Commissioning Gateway
SKF Wireless Machine Condition Sensor
19
Service Manual
Figure 10
.
Connect the gateway to the LAN.
•
Click the
Write Ethernet Information’s >>
button to update the gateway with the
LAN settings. The gateway should be configured now to communicate using the
LAN.
•
Disconnect the Ethernet cable from the configuration computer and connect it
directly to your LAN.
•
Launch the gateway’s web page in the Device Manager host computer to continue
configuring the gateway.
•
Modify the
Ethernet / User Datagram Protocol
(UDP) port number to the SKF
default port of
20004
for the Device Manager connection.
Figure 11
.
Ethernet / UDP Port Number.
•
Verify the current network settings by expanding
Parameter
>
Wireless
Communication
>
Setup
. If the gateway is from SKF, the default commissioning
network ID of 1229 will display and the default Join Keys will be present, but
masked. (The Join Keys are shown on the following page.)
If the
Network ID
is
1229
and the
Join Keys
of the commissioning network are present,
the network is ready for the new sensors to join the commissioning network.
If the gateway is
not
from SKF, or you see a different Network ID,
instructions for changing the network settings are provided below
in the section, “Steps to configure a commissioning gateway.”