The P+F Gateway’s Web Page
Preparing a Commissioning Gateway
20
SKF Wireless Machine Condition Sensor
Service Manual
Figure 12
.
Verify the Network ID.
If the P+F gateway is NOT from SKF, or if the Network ID is different, then
complete the following steps.
Steps to configure a commissioning gateway:
Set
DIP switch 8
to the
up
position to disable the security
mode and enable the write
function.
Expand
Parameter
>
Wireless
Communication
>
Setup
.
Change the gateway’s
Network ID
and
Join Key
to the SKF defaults
for the commissioning network.
Note: The gateway requires the
Network ID and Join Key to be set
together.
SKF Factory Network ID: 1229
SKF Factory Join Key:
44555354
4E455457
4F524B53
524F434B
Click
Write Join Information
and
confirm the prompts.
When the upload is done, return
DIP switch 8
to the
down
position
to disable the write function and
enable the security mode again.