4.4
Bus termination
If the inclinometer is connected at the end or beginning of the bus for higher transmission baud
rates (
≥50 kBaud/s) a termination resistor of 120 Ohm must be used in order to prevent the
reflection of information back into the CAN bus.
The bus wires can be routed in parallel, twisted or shielded form in accordance with the
electromagnetic compatibility requirements. A single line structure minimizes reflection.
The following diagram shows the components for the physical layer of a two-wire CAN-bus:
4.5
Measurement axis
IK360 (1 axis)
Measurement axis and mid angle position
(factory setting ~ connector facing down)
CAN Low wire
CAN High wire
IK360
inclinometer
IK360
inclinometer
120
Ω
120Ω
Other CAN nodes
PLC
CANope
n
Master