Troubleshooting
Fixed-
‘mounted
breaker
Draw-out
circuit
breaker
Disturbance
Possible cause(s)
Remedy
X
X
Circuit breaker cannot be
closed.
Circuit breaker
not
ready to
close.
"Ready-to-close" indicator
shows:
1.
Closing spring not charged
Charge closing spring
X
X
2.
Undervoltage release not ener-
gized.
Energize undervoltage release
X
X
3.
Electrical closing interlock
effective
Switch off control voltage for
interlocking
X
X
4.
Key lock engaged
(optional accessory)
Unlock
X
X
5.
Padlocks installed
Remove padlocks
X
X
6.
"EMERGENCY OPEN" button
engaged in operating position
(accessories)
Release "EMERGENCY OPEN"
button by rotating it
X
X
7.
Lockout effective against closing
when cubicle door is open
(accessories)
Close cubicle door
X
X
8.
Electronic
trip unit
missing or
incorrectly installed
Install electronic
trip unit
properly
X
X
9.
Shunt trip energized
De-energize shunt trip
X
10. Racking handle withdrawn
Rack circuit breaker into discon-
nected, test or connected position,
unlatch crank and push it fully in
X
X
11. Closing coil energized
Closing coil has to be deenergized
shortly for reclosing
X
X
12. Mutual mechanical circuit breaker
interlocks effective (accessories)
Open second circuit breaker or rack
into disconnected position
Summary of Contents for UL 489
Page 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Page 63: ...7 2 Horizontal connectors 0733_nu top view ...
Page 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Page 65: ...7 4 Front connectors 0736_nu front view top view ...
Page 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Page 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Page 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Page 69: ...7 8 2500 0738_nu LH side view front view ...
Page 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Page 72: ...7 11 0495 2_nu top view top view ...
Page 73: ...7 12 0495 3_nu top view rear view ...
Page 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Page 76: ...7 15 Frame size II III 0496_nu ...
Page 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Page 78: ...7 17 0746_nu rear view top view ...
Page 79: ...7 18 0747_nu bottom view ...
Page 80: ...7 19 0748_nu ...
Page 81: ...7 20 0749_nu ...
Page 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Page 86: ...7 25 7 8 Frame size III draw out version ...
Page 87: ...7 26 ...
Page 88: ...7 27 ...
Page 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Page 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Page 92: ...7 31 WLNCT3 ...
Page 107: ...9 5 I tripping Ground fault tripping ...
Page 351: ......