9 – 77
Exception Status Bits
The Exception Status Bits are accessed using the following functions:
07 Read Exception Status - Reads the state of the Exception Status Bits
Further information about the application of these inputs and outputs is given in the "WL Modbus RTU Communication Manual" WL
Low Voltage Power Circuit Breaker catalog.
Catalog number
9.2.2.6 Metering function
PLUS
Trip units ETU745 - ETU776 can be equipped with a metering function
PLUS
. This, however, requires external voltage transformers
providing a three-phase metering voltage (such as the Siemens WL3VT).
This data can be shown on the display of the trip units, transmitted by the COM module via PROFIBUS DP, PROFINET IO, Modbus RTU,
or Modbus TCP, and passed on to the outputs of external
c
modules. Based on this data, conclusions can be drawn about the
condition of the power system. To use the metering function without communication, an external 24 V auxiliary voltage supply is required.
In addition to the values for the currents, the metering function
PLUS
provides data on voltages, powers, energy values, power factors and
frequency via the
c
for further processing.
Bit
Description
0
Excessive breaker contact wear
1
Communication with trip unit OK
2
COM16 is OK
3 - 7
Reserved
Catalog No.
WL Breaker Configuration Software
POWERCONFIG
NOTICE
High voltages may damage the MeteringPLUS module.
The secondary voltage of the external voltage transformers must not exceed 150 V AC RMS or 300 V AC peak value.
Summary of Contents for UL 489
Page 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Page 63: ...7 2 Horizontal connectors 0733_nu top view ...
Page 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Page 65: ...7 4 Front connectors 0736_nu front view top view ...
Page 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Page 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Page 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Page 69: ...7 8 2500 0738_nu LH side view front view ...
Page 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Page 72: ...7 11 0495 2_nu top view top view ...
Page 73: ...7 12 0495 3_nu top view rear view ...
Page 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Page 76: ...7 15 Frame size II III 0496_nu ...
Page 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Page 78: ...7 17 0746_nu rear view top view ...
Page 79: ...7 18 0747_nu bottom view ...
Page 80: ...7 19 0748_nu ...
Page 81: ...7 20 0749_nu ...
Page 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Page 86: ...7 25 7 8 Frame size III draw out version ...
Page 87: ...7 26 ...
Page 88: ...7 27 ...
Page 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Page 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Page 92: ...7 31 WLNCT3 ...
Page 107: ...9 5 I tripping Ground fault tripping ...
Page 351: ......