19 – 14
19.2.4
Function check
- Close the cubicle doors
- Charge closing spring of circuit breakers to be interlocked
- Test the various possibilities of the planned interlocking configuration one after the other
- Re-adjust Bowden cables if necessary
Then:
- Discharge the closing spring of the circuit breakers to be interlocked
Catalog Numbers
Note
The following maintenance points must be followed:
1
The adjustment of the Bowden cables needs to be checked after the first 100 breaker operations and must be readjusted if
necessary.
2
The adjustment of the interlocking device needs to be checked and, if necessary, readjusted every 1000 operations or at least
once every year.
3
During the inspection, the Bowden cables have to be checked against kinks and abrasions, split wires of the exposed
steel cable, damage to the cable housing and the adjustment unit (tube setting with thread and nut) and have to be readjusted
if necessary. In addition, the movability of movable parts of the interlocking device in their bearings needs to be examined.
4
In extreme environmental conditions (e.g. increased environmental temperature or exposure to chemicals) maintenance checks
needs to be performed more frequently.
5
When maintaining the circuit breaker, check the operation of the interlock device and replace as necessary. See table
.
Mechanical Interlocking
Catlog number
Mechanical interlock assembly for drawout circuit breakers (FS I, II, and III)
WLNTLK
Mechanical interlock assembly for fixed-mounted circuit breakers (FS I)
WLNTLKF1
Mechanical interlock assembly for fixed-mounted circuit breakers (FS II and III)
WLNTLKF
Qty.(1) Bowden Cable - 2m
WLNTLWIRE2
Qty.(1) Bowden Cable - 4.5m
WLNTLWIRE4
Summary of Contents for UL 489
Page 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Page 63: ...7 2 Horizontal connectors 0733_nu top view ...
Page 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Page 65: ...7 4 Front connectors 0736_nu front view top view ...
Page 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Page 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Page 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Page 69: ...7 8 2500 0738_nu LH side view front view ...
Page 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Page 72: ...7 11 0495 2_nu top view top view ...
Page 73: ...7 12 0495 3_nu top view rear view ...
Page 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Page 76: ...7 15 Frame size II III 0496_nu ...
Page 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Page 78: ...7 17 0746_nu rear view top view ...
Page 79: ...7 18 0747_nu bottom view ...
Page 80: ...7 19 0748_nu ...
Page 81: ...7 20 0749_nu ...
Page 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Page 86: ...7 25 7 8 Frame size III draw out version ...
Page 87: ...7 26 ...
Page 88: ...7 27 ...
Page 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Page 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Page 92: ...7 31 WLNCT3 ...
Page 107: ...9 5 I tripping Ground fault tripping ...
Page 351: ......