19 – 1
19
Mechanical circuit breaker interlocking
Mechanical interlocking module
(1)
Cradle
(2)
Fixed-mounted breaker
19.1
Configurations
A maximum of three circuit breakers may be interlocked.
NOTE
For proper function of the interlocking device, the following minimum prerequisites have to be met:
1
Bowden cables are to be laid out as straight and as unbowed as possible.
2
Bending radii of the Bowden cables must exceed > 20" (500 mm).
3
The total curvature of the Bowden cable must not exceed 540 degrees.
4
When stacking interlocked circuit breakers vertically, the interlocking devices shall be vertically aligned with each other.
5
Circuit breakers intended to be interlocked must be positioned so that Bowden cables of 6 ft or 15 ft (2 m or 4.5 m) length can
be laid out per the above requirements 1-4.
6
Before adjusting the interlocking device, the Bowden cables must be secured, e.g. using cable ties.
7
Adequate spacing is required to provide enough room for adjustment of the interlocking device.
(2)
(1)
Summary of Contents for UL 489
Page 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Page 63: ...7 2 Horizontal connectors 0733_nu top view ...
Page 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Page 65: ...7 4 Front connectors 0736_nu front view top view ...
Page 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Page 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Page 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Page 69: ...7 8 2500 0738_nu LH side view front view ...
Page 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Page 72: ...7 11 0495 2_nu top view top view ...
Page 73: ...7 12 0495 3_nu top view rear view ...
Page 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Page 76: ...7 15 Frame size II III 0496_nu ...
Page 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Page 78: ...7 17 0746_nu rear view top view ...
Page 79: ...7 18 0747_nu bottom view ...
Page 80: ...7 19 0748_nu ...
Page 81: ...7 20 0749_nu ...
Page 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Page 86: ...7 25 7 8 Frame size III draw out version ...
Page 87: ...7 26 ...
Page 88: ...7 27 ...
Page 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Page 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Page 92: ...7 31 WLNCT3 ...
Page 107: ...9 5 I tripping Ground fault tripping ...
Page 351: ......