9 – 98
9.3
External voltage supply
The basic protective functions (L, S, I, & G) of the electronic trip units do not require an auxiliary power supply.
To use the extended functions of trip units ETU745 - 776 requiring data exchange via the
c
, an external 24 V DC (class 2) voltage
supply must be connected.
Connection
Version A: Connection to secondary terminal block X8 (preferred version)
Version B: Connection to any
c
module
Requirements
The external voltage supply with 24 V DC must fulfill at least the requirements of UL class 2.
The Siemens power supply listed below may be used to supply power to a single circuit breaker. A second circuit breaker requires its own
power supply.
The external power supply used for electronic components must not be used to supply the motor-operated mechanism.
When using voltage supply units from other manufacturers, the following conditions must be fulfilled:
- Primary-switched-mode power supply unit
- 24 V DC, ± 3 %
- Current rating: minimum 3.7A per circuit breaker
- EMC according to: IEC 61000-4-4, 4kV on main side; IEC 61000-4-5, 4kV line-to-earth, 2kV line-to-line.
Catalog number
Power supply
Catalog No.
MLFB
120/230 VAC / 24 VDC,
3.8A SITOP PSU100C NEC CLASS 2
WLSITOP1
6EP1332-5BA20
Summary of Contents for UL 489
Page 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Page 63: ...7 2 Horizontal connectors 0733_nu top view ...
Page 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Page 65: ...7 4 Front connectors 0736_nu front view top view ...
Page 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Page 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Page 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Page 69: ...7 8 2500 0738_nu LH side view front view ...
Page 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Page 72: ...7 11 0495 2_nu top view top view ...
Page 73: ...7 12 0495 3_nu top view rear view ...
Page 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Page 76: ...7 15 Frame size II III 0496_nu ...
Page 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Page 78: ...7 17 0746_nu rear view top view ...
Page 79: ...7 18 0747_nu bottom view ...
Page 80: ...7 19 0748_nu ...
Page 81: ...7 20 0749_nu ...
Page 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Page 86: ...7 25 7 8 Frame size III draw out version ...
Page 87: ...7 26 ...
Page 88: ...7 27 ...
Page 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Page 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Page 92: ...7 31 WLNCT3 ...
Page 107: ...9 5 I tripping Ground fault tripping ...
Page 351: ......