9 – 71
Changing the communication parameters
The communication parameters of the COM16 module can be changed by writing the required parameters (baud rate, serial configuration
and Modbus RTU communication address) in data set 160.
Note: Registers not listed are reserved.
For details on data formats and properties, see "SENTRON WL VL circuit breakers with communication capability MODBUS" manual.
Dataset 160
Communication Parameters
Address: A000
hex, Registers: 36, Access: Read / Write
Register
Byte
HIGH/
LOW
Byte
Description
Data
point
Source
WL
Source
VL
1
Source
VL
2
Format
Length Scaling
40960
0
Header; value 0x00 00 00 00
—
COM16
COM11
COM21
—
32
—
40962
4
HIGH
Reserved
—
—
—
—
—
8
—
5
LOW
Modbus RTU address
5
COM16
COM11
COM21
Unsigned char
8
0
40963
6
HIGH
Basic data type (1, 2 or 3)
6
COM16
COM11
COM21
Unsigned char
8
—
7
LOW
Reserved
—
—
—
—
—
8
—
40964
8
Changeable data points in the
basic data
7
COM16
COM11
COM21
Unsigned char
224
—
40984
48
HIGH
Modbus baud rate
427
COM16
COM11
COM21
Unsigned char
8
—
49
LOW
Modbus parity
428
COM16
COM11
COM21
Unsigned char
8
—
40994
68
HIGH
Property for Byte 49
—
COM16
COM11
COM21
Property byte
8
—
69
LOW
Property for Byte 48
—
COM16
COM11
COM21
Property byte
8
—
40995
70
HIGH
Reserved
—
—
—
—
Property byte
8
—
71
LOW
Property for Byte 5
—
COM16
COM11
COM21
Property byte
8
—
40996
72
HIGH
Property for Byte 6
—
COM16
COM11
COM21
Property byte
8
—
73
LOW
Reserved
—
—
—
—
Property byte
8
—
40997
74
HIGH
Property for Byte 8
—
COM16
COM11
COM21
Property byte
8
—
75
LOW
Reserved
—
—
—
—
Property byte
8
—
78
Total Bytes
Summary of Contents for UL 489
Page 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Page 63: ...7 2 Horizontal connectors 0733_nu top view ...
Page 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Page 65: ...7 4 Front connectors 0736_nu front view top view ...
Page 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Page 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Page 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Page 69: ...7 8 2500 0738_nu LH side view front view ...
Page 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Page 72: ...7 11 0495 2_nu top view top view ...
Page 73: ...7 12 0495 3_nu top view rear view ...
Page 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Page 76: ...7 15 Frame size II III 0496_nu ...
Page 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Page 78: ...7 17 0746_nu rear view top view ...
Page 79: ...7 18 0747_nu bottom view ...
Page 80: ...7 19 0748_nu ...
Page 81: ...7 20 0749_nu ...
Page 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Page 86: ...7 25 7 8 Frame size III draw out version ...
Page 87: ...7 26 ...
Page 88: ...7 27 ...
Page 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Page 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Page 92: ...7 31 WLNCT3 ...
Page 107: ...9 5 I tripping Ground fault tripping ...
Page 351: ......