Primary injection testing
Qualified Personnel
For the purpose of this instruction manual and these product labels, a
"
qualified person
"
is one who is familiar with the installation, construc-
tion and operation of the equipment and the hazards involved and who,
in addition, has the following qualifications:
a) Is trained and authorized to energize, de-energize, clear, ground and label circuits and equipment in accordance with established
safety practices.
b) Is trained in the proper care and use of protective equipment in accordance with established safety practices.
c) Is trained in administering first aid.
Observe Circuit Breaker Settings
The WL circuit breaker ships from the factory with the lowest possible settings. For exisiting circuit breaker installations, it is important to
notice and take record of all customer settings of the circuit breaker before performing any testing. These settings should be restored at the
conclusion of all inspection and testing.
Proper handling of WL Circuit Breakers
It is important to adhere to all rigging and transportation requirements for Siemens type WL circuit breakers
DANGER
Hazardous voltage.
Will cause death, serious personal injury, or equipment/property damage.
Turn off and lock out all power supplying this equipment before working on this device.
Only qualified personnel should work on this equipment, after becoming thoroughly familiar with all warnings, safety
notices, and maintenance procedures contained herein and on the devices.
The successful and safe operation of this equipment is dependent on proper handling, installation, operation and
maintenance.
CAUTION
Fragile Assembly
Finger Clusters may become damaged or disassembled. Connection may overheat and cause property damage.
Do not rest breaker on finger clusters; avoid impact to finger clusters.
Do not insert busbars wider than 0.40 inch [10 mm] into the finger clusters for the following circuit breaker frames:
WLN2A308, WLN2A316, WLS2A308, WLS2A316, WLS2D308, WLS2D312, WLS2D316, WLH2A308, WLH2A316, WLH2S308,
WLH2S316, WLH2Z308, WLH2Z316, WLL2A308, WLL2A316, WLL2D308, WLL2D312, WLL2D316
Do not insert busbars wider than 0.59 inch [15 mm] into the finger clusters for the following circuit breaker frames:
WLS1D308, WLS1D312, WLS1D316, WLS1D320, WLL1D308, WLL1D312, WLL1D316, WLL1D320, WLL1Z308, WLL1Z312,
WLL1Z316, WLL1Z320, WLN2A320, WLS2A320, WLS2D320, WLH2A320, WLH2S320, WLH2Z320, WLL2A320, WLL2D320,
WLF2A308, WLF2A316, WLF2A320, WLF2S308, WLF2S316, WLF2S320
Do not insert busbars wider than 1.18 inch [30 mm] into the finger clusters for the following circuit breaker frames:
WLN2A332, WLS2A332, WLS2D330, WLH2A332, WLH2S332, WLH2Z325, WLH2Z330, WLL2A332, WLL2D330, WLC2D308,
WLC2D312, WLC2D316, WLC2D320, WLC2D325, WLC2D330, WLL3A340, WLL3A350, WLL3S340, WLL3S350, WLL3D340,
WLL3D350, WLL3Z340, WLL3Z350, WLF3A332, WLF3A340, WLF3A350, WLF3S332, WLF3S340, WLF3S350, WLM3A340,
WLM3A350, WLC3D340, WLC3D350.
Visually inspect all finger clusters prior to installing drawout circuit breakers.
Do not energize a circuit breaker with a damaged finger cluster assembly.
Summary of Contents for UL 489
Page 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Page 63: ...7 2 Horizontal connectors 0733_nu top view ...
Page 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Page 65: ...7 4 Front connectors 0736_nu front view top view ...
Page 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Page 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Page 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Page 69: ...7 8 2500 0738_nu LH side view front view ...
Page 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Page 72: ...7 11 0495 2_nu top view top view ...
Page 73: ...7 12 0495 3_nu top view rear view ...
Page 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Page 76: ...7 15 Frame size II III 0496_nu ...
Page 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Page 78: ...7 17 0746_nu rear view top view ...
Page 79: ...7 18 0747_nu bottom view ...
Page 80: ...7 19 0748_nu ...
Page 81: ...7 20 0749_nu ...
Page 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Page 86: ...7 25 7 8 Frame size III draw out version ...
Page 87: ...7 26 ...
Page 88: ...7 27 ...
Page 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Page 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Page 92: ...7 31 WLNCT3 ...
Page 107: ...9 5 I tripping Ground fault tripping ...
Page 351: ......