9 – 100
9.4.3
Connecting
(1)
Test connector of the trip unit
(2)
40-pole ribbon cable with plugs
(3)
Voltage supply
(4)
Handheld test device
9.4.4
Voltage supply
The handheld test device is supplied by a 110 - 125 V AC network.
9.4.5
Operation
The status test begins after the voltage supply has been connected. The various components and parameters of the trip unit are queried. If
the status test has been completed successfully, the "ETU STATUS" LED will light up continuously.
If it has not been completed successfully, the "ETU STATUS" LED will flash. The type of flashing indicates what type of fault is present.
The status test can be repeated any time by pressing the "START" button for at least three seconds.
It is also possible to test a trip unit that is already activated, i.e. one that is supplied by an external voltage source. However, it must be taken
into account that the "ETU STATUS" LED may briefly flash twice when the status test result is displayed, even if there have not been any
faults. As a precaution, the status test should be repeated without external voltage supply.
NOTE
Observe the connecting sequence.
Malfunctions and incorrect test results may result if the sequence is not observed.
Indicator
Significance
1 x briefly, pause
Handheld test device defective
2 x briefly, pause
Trip unit defective
4 x briefly, pause
- Parameters not set correctly
- Current sensor not properly connected
- Wrong Rating Plug
- Missing Rating Plug
5 x briefly, pause
- Tripping coil F5 not properly connected
- Coil defective
1
3
2
Summary of Contents for UL 489
Page 36: ...5 21 Frame size II 3000 A Frame size III 1 Holes 14 mm 0720 1 0721_nu ...
Page 63: ...7 2 Horizontal connectors 0733_nu top view ...
Page 64: ...7 3 Rear vertical connectors 0734_nu top view rear view ...
Page 65: ...7 4 Front connectors 0736_nu front view top view ...
Page 66: ...7 5 Front connectors and pressure wire terminals 0737_nu top view front view ...
Page 67: ...7 6 7 2 Frame size II fixed mounted version 0494 3_nu ...
Page 68: ...7 7 Class C always 0494 5_nu top view rear view ...
Page 69: ...7 8 2500 0738_nu LH side view front view ...
Page 71: ...7 10 7 4 Frame size III fixed mounted version 0495 1_nu LH side view ...
Page 72: ...7 11 0495 2_nu top view top view ...
Page 73: ...7 12 0495 3_nu top view rear view ...
Page 75: ...7 14 7 5 Door cut outs fixed mounted circuit breaker Frame size I 0735_nu ...
Page 76: ...7 15 Frame size II III 0496_nu ...
Page 77: ...7 16 7 6 Frame size I draw out version 0745_nu ...
Page 78: ...7 17 0746_nu rear view top view ...
Page 79: ...7 18 0747_nu bottom view ...
Page 80: ...7 19 0748_nu ...
Page 81: ...7 20 0749_nu ...
Page 82: ...7 21 7 7 Frame size II draw out version 0490 1_ul ...
Page 86: ...7 25 7 8 Frame size III draw out version ...
Page 87: ...7 26 ...
Page 88: ...7 27 ...
Page 89: ...7 28 7 9 Door cut outs for draw out circuit breakers Frame size I 0750_nu ...
Page 91: ...7 30 7 11 External sensor for neutral conductor WLNCT2 ...
Page 92: ...7 31 WLNCT3 ...
Page 107: ...9 5 I tripping Ground fault tripping ...
Page 351: ......